45 Amp Cable Size at 10 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 1.67V (0.24%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 1.72V (0.25%)
Voltage at Load688.3 VLine Loss: 130.0 W
Max Power & Breaker53.78 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11.12 V (1.61%)678.9 V18.34 V (2.66%)866.7 WDrop High
2.5 mm²24 A18 A6.67 V (0.97%)683.3 V11.01 V (1.59%)520.0 WDrop High
4 mm²32 A25 A4.17 V (0.6%)685.8 V6.88 V (1.0%)325.0 WDrop High
6 mm²41 A32 A2.78 V (0.4%)687.2 V4.59 V (0.66%)216.7 WDrop High
10 mm²57 A44 A1.67 V (0.24%)688.3 V2.75 V (0.4%)130.0 W✓ OK (≤3%)
16 mm²76 A59 A1.04 V (0.15%)689.0 V1.72 V (0.25%)81.3 W✓ OK (≤3%)
25 mm²101 A78 A0.67 V (0.1%)689.3 V1.1 V (0.16%)52.0 W✓ OK (≤3%)
35 mm²125 A97 A0.48 V (0.07%)689.5 V0.79 V (0.11%)37.1 W✓ OK (≤3%)
50 mm²151 A118 A0.33 V (0.05%)689.7 V0.55 V (0.08%)26.0 W✓ OK (≤3%)
70 mm²192 A150 A0.24 V (0.03%)689.8 V0.39 V (0.06%)18.6 W✓ OK (≤3%)
95 mm²232 A181 A0.18 V (0.03%)689.8 V0.29 V (0.04%)13.7 W✓ OK (≤3%)
120 mm²269 A210 A0.14 V (0.02%)689.9 V0.23 V (0.03%)10.8 W✓ OK (≤3%)
150 mm²309 A241 A0.11 V (0.02%)689.9 V0.18 V (0.03%)8.7 W✓ OK (≤3%)
185 mm²353 A275 A0.09 V (0.01%)689.9 V0.15 V (0.02%)7.0 W✓ OK (≤3%)
240 mm²415 A324 A0.07 V (0.01%)689.9 V0.11 V (0.02%)5.4 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.01%)689.9 V0.09 V (0.01%)4.3 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.01%)690.0 V0.07 V (0.01%)3.3 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 10 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 45A at 10 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 45A over 10m at 690V (voltage drop: 1.67V or 0.24%).

What is the power capacity of 45A at 690V?

At unity power factor, 45A at 690V supports 53.78 kW with a standard 45A circuit breaker.