⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

20 Amp Cable Size at 10 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 20 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)2.5 mm²Drop: 2.97V (0.43%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 3.06V (0.44%)
Voltage at Load687.0 VLine Loss: 102.7 W
Max Power & Breaker23.9 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4.94 V (0.72%)685.1 V8.15 V (1.18%)171.2 WDrop High
2.5 mm²24 A18 A2.97 V (0.43%)687.0 V4.89 V (0.71%)102.7 W✓ OK (≤3%)
4 mm²32 A25 A1.85 V (0.27%)688.1 V3.06 V (0.44%)64.2 W✓ OK (≤3%)
6 mm²41 A32 A1.24 V (0.18%)688.8 V2.04 V (0.3%)42.8 W✓ OK (≤3%)
10 mm²57 A44 A0.74 V (0.11%)689.3 V1.22 V (0.18%)25.7 W✓ OK (≤3%)
16 mm²76 A59 A0.46 V (0.07%)689.5 V0.76 V (0.11%)16.1 W✓ OK (≤3%)
25 mm²101 A78 A0.3 V (0.04%)689.7 V0.49 V (0.07%)10.3 W✓ OK (≤3%)
35 mm²125 A97 A0.21 V (0.03%)689.8 V0.35 V (0.05%)7.3 W✓ OK (≤3%)
50 mm²151 A118 A0.15 V (0.02%)689.9 V0.24 V (0.04%)5.1 W✓ OK (≤3%)
70 mm²192 A150 A0.11 V (0.02%)689.9 V0.17 V (0.03%)3.7 W✓ OK (≤3%)
95 mm²232 A181 A0.08 V (0.01%)689.9 V0.13 V (0.02%)2.7 W✓ OK (≤3%)
120 mm²269 A210 A0.06 V (0.01%)689.9 V0.1 V (0.01%)2.1 W✓ OK (≤3%)
150 mm²309 A241 A0.05 V (0.01%)690.0 V0.08 V (0.01%)1.7 W✓ OK (≤3%)
185 mm²353 A275 A0.04 V (0.01%)690.0 V0.07 V (0.01%)1.4 W✓ OK (≤3%)
240 mm²415 A324 A0.03 V (0.0%)690.0 V0.05 V (0.01%)1.1 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.0%)690.0 V0.04 V (0.01%)0.9 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.0%)690.0 V0.03 V (0.0%)0.6 W✓ OK (≤3%)

FAQ — 20 Amp Cable Size at 10 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 20A at 10 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2.5 mm² copper cable for 20A over 10m at 690V (voltage drop: 2.97V or 0.43%).

What is the power capacity of 20A at 690V?

At unity power factor, 20A at 690V supports 23.9 kW with a standard 20A circuit breaker.