⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

25 Amp Cable Size at 10 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 2.32V (0.34%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 3.82V (0.55%)
Voltage at Load687.7 VLine Loss: 100.3 W
Max Power & Breaker29.88 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6.18 V (0.9%)683.8 V10.19 V (1.48%)267.5 WDrop High
2.5 mm²24 A18 A3.71 V (0.54%)686.3 V6.11 V (0.89%)160.5 WDrop High
4 mm²32 A25 A2.32 V (0.34%)687.7 V3.82 V (0.55%)100.3 W✓ OK (≤3%)
6 mm²41 A32 A1.54 V (0.22%)688.5 V2.55 V (0.37%)66.9 W✓ OK (≤3%)
10 mm²57 A44 A0.93 V (0.13%)689.1 V1.53 V (0.22%)40.1 W✓ OK (≤3%)
16 mm²76 A59 A0.58 V (0.08%)689.4 V0.96 V (0.14%)25.1 W✓ OK (≤3%)
25 mm²101 A78 A0.37 V (0.05%)689.6 V0.61 V (0.09%)16.1 W✓ OK (≤3%)
35 mm²125 A97 A0.26 V (0.04%)689.7 V0.44 V (0.06%)11.5 W✓ OK (≤3%)
50 mm²151 A118 A0.19 V (0.03%)689.8 V0.31 V (0.04%)8.0 W✓ OK (≤3%)
70 mm²192 A150 A0.13 V (0.02%)689.9 V0.22 V (0.03%)5.7 W✓ OK (≤3%)
95 mm²232 A181 A0.1 V (0.01%)689.9 V0.16 V (0.02%)4.2 W✓ OK (≤3%)
120 mm²269 A210 A0.08 V (0.01%)689.9 V0.13 V (0.02%)3.3 W✓ OK (≤3%)
150 mm²309 A241 A0.06 V (0.01%)689.9 V0.1 V (0.01%)2.7 W✓ OK (≤3%)
185 mm²353 A275 A0.05 V (0.01%)689.9 V0.08 V (0.01%)2.2 W✓ OK (≤3%)
240 mm²415 A324 A0.04 V (0.01%)690.0 V0.06 V (0.01%)1.7 W✓ OK (≤3%)
300 mm²477 A372 A0.03 V (0.0%)690.0 V0.05 V (0.01%)1.3 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.0%)690.0 V0.04 V (0.01%)1.0 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 10 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 25A at 10 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 25A over 10m at 690V (voltage drop: 2.32V or 0.34%).

What is the power capacity of 25A at 690V?

At unity power factor, 25A at 690V supports 29.88 kW with a standard 25A circuit breaker.