45 Amp Cable Size at 120 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 20.02V (2.9%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 20.64V (2.99%)
Voltage at Load670.0 VLine Loss: 1560.1 W
Max Power & Breaker53.78 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A133.44 V (19.34%)556.6 V220.11 V (31.9%)10400.4 WDrop High
2.5 mm²24 A18 A80.06 V (11.6%)609.9 V132.07 V (19.14%)6240.2 WDrop High
4 mm²32 A25 A50.04 V (7.25%)640.0 V82.54 V (11.96%)3900.2 WDrop High
6 mm²41 A32 A33.36 V (4.83%)656.6 V55.03 V (7.97%)2600.1 WDrop High
10 mm²57 A44 A20.02 V (2.9%)670.0 V33.02 V (4.78%)1560.1 W✓ OK (≤3%)
16 mm²76 A59 A12.51 V (1.81%)677.5 V20.64 V (2.99%)975.0 W✓ OK (≤3%)
25 mm²101 A78 A8.01 V (1.16%)682.0 V13.21 V (1.91%)624.0 W✓ OK (≤3%)
35 mm²125 A97 A5.72 V (0.83%)684.3 V9.43 V (1.37%)445.7 W✓ OK (≤3%)
50 mm²151 A118 A4.0 V (0.58%)686.0 V6.6 V (0.96%)312.0 W✓ OK (≤3%)
70 mm²192 A150 A2.86 V (0.41%)687.1 V4.72 V (0.68%)222.9 W✓ OK (≤3%)
95 mm²232 A181 A2.11 V (0.31%)687.9 V3.48 V (0.5%)164.2 W✓ OK (≤3%)
120 mm²269 A210 A1.67 V (0.24%)688.3 V2.75 V (0.4%)130.0 W✓ OK (≤3%)
150 mm²309 A241 A1.33 V (0.19%)688.7 V2.2 V (0.32%)104.0 W✓ OK (≤3%)
185 mm²353 A275 A1.08 V (0.16%)688.9 V1.78 V (0.26%)84.3 W✓ OK (≤3%)
240 mm²415 A324 A0.83 V (0.12%)689.2 V1.38 V (0.2%)65.0 W✓ OK (≤3%)
300 mm²477 A372 A0.67 V (0.1%)689.3 V1.1 V (0.16%)52.0 W✓ OK (≤3%)
400 mm²570 A445 A0.5 V (0.07%)689.5 V0.83 V (0.12%)39.0 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 120 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 45A at 120 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 45A over 120m at 690V (voltage drop: 20.02V or 2.9%).

What is the power capacity of 45A at 690V?

At unity power factor, 45A at 690V supports 53.78 kW with a standard 45A circuit breaker.