45 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 1.16V (2.41%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 1.36V (2.84%)
Voltage at Load46.8 VLine Loss: 52.0 W
Max Power & Breaker2.16 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A19.26 V (40.12%)28.7 V31.77 V (66.19%)866.7 WDrop High
2.5 mm²24 A18 A11.56 V (24.08%)36.4 V19.06 V (39.71%)520.0 WDrop High
4 mm²32 A25 A7.22 V (15.05%)40.8 V11.91 V (24.82%)325.0 WDrop High
6 mm²41 A32 A4.81 V (10.03%)43.2 V7.94 V (16.55%)216.7 WDrop High
10 mm²57 A44 A2.89 V (6.02%)45.1 V4.77 V (9.93%)130.0 WDrop High
16 mm²76 A59 A1.81 V (3.76%)46.2 V2.98 V (6.21%)81.3 W~ ≤5%
25 mm²101 A78 A1.16 V (2.41%)46.8 V1.91 V (3.97%)52.0 W✓ OK (≤3%)
35 mm²125 A97 A0.83 V (1.72%)47.2 V1.36 V (2.84%)37.1 W✓ OK (≤3%)
50 mm²151 A118 A0.58 V (1.2%)47.4 V0.95 V (1.99%)26.0 W✓ OK (≤3%)
70 mm²192 A150 A0.41 V (0.86%)47.6 V0.68 V (1.42%)18.6 W✓ OK (≤3%)
95 mm²232 A181 A0.3 V (0.63%)47.7 V0.5 V (1.05%)13.7 W✓ OK (≤3%)
120 mm²269 A210 A0.24 V (0.5%)47.8 V0.4 V (0.83%)10.8 W✓ OK (≤3%)
150 mm²309 A241 A0.19 V (0.4%)47.8 V0.32 V (0.66%)8.7 W✓ OK (≤3%)
185 mm²353 A275 A0.16 V (0.33%)47.8 V0.26 V (0.54%)7.0 W✓ OK (≤3%)
240 mm²415 A324 A0.12 V (0.25%)47.9 V0.2 V (0.41%)5.4 W✓ OK (≤3%)
300 mm²477 A372 A0.1 V (0.2%)47.9 V0.16 V (0.33%)4.3 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.15%)47.9 V0.12 V (0.25%)3.3 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 45A at 15 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 45A over 15m at 48V (voltage drop: 1.16V or 2.41%).

What is the power capacity of 45A at 48V?

At unity power factor, 45A at 48V supports 2.16 kW with a standard 45A circuit breaker.