45 Amp Cable Size at 45 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 1.24V (2.58%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 1.19V (2.48%)
Voltage at Load46.8 VLine Loss: 55.7 W
Max Power & Breaker2.16 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A57.78 V (120.38%)0.0 V95.31 V (198.56%)2600.1 WDrop High
2.5 mm²24 A18 A34.67 V (72.22%)13.3 V57.19 V (119.14%)1560.1 WDrop High
4 mm²32 A25 A21.67 V (45.14%)26.3 V35.74 V (74.46%)975.0 WDrop High
6 mm²41 A32 A14.45 V (30.09%)33.6 V23.83 V (49.64%)650.0 WDrop High
10 mm²57 A44 A8.67 V (18.06%)39.3 V14.3 V (29.78%)390.0 WDrop High
16 mm²76 A59 A5.42 V (11.29%)42.6 V8.94 V (18.62%)243.8 WDrop High
25 mm²101 A78 A3.47 V (7.22%)44.5 V5.72 V (11.91%)156.0 WDrop High
35 mm²125 A97 A2.48 V (5.16%)45.5 V4.08 V (8.51%)111.4 WDrop High
50 mm²151 A118 A1.73 V (3.61%)46.3 V2.86 V (5.96%)78.0 W~ ≤5%
70 mm²192 A150 A1.24 V (2.58%)46.8 V2.04 V (4.25%)55.7 W✓ OK (≤3%)
95 mm²232 A181 A0.91 V (1.9%)47.1 V1.5 V (3.14%)41.1 W✓ OK (≤3%)
120 mm²269 A210 A0.72 V (1.5%)47.3 V1.19 V (2.48%)32.5 W✓ OK (≤3%)
150 mm²309 A241 A0.58 V (1.2%)47.4 V0.95 V (1.99%)26.0 W✓ OK (≤3%)
185 mm²353 A275 A0.47 V (0.98%)47.5 V0.77 V (1.61%)21.1 W✓ OK (≤3%)
240 mm²415 A324 A0.36 V (0.75%)47.6 V0.6 V (1.24%)16.3 W✓ OK (≤3%)
300 mm²477 A372 A0.29 V (0.6%)47.7 V0.48 V (0.99%)13.0 W✓ OK (≤3%)
400 mm²570 A445 A0.22 V (0.45%)47.8 V0.36 V (0.74%)9.8 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 45 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 45A at 45 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 45A over 45m at 48V (voltage drop: 1.24V or 2.58%).

What is the power capacity of 45A at 48V?

At unity power factor, 45A at 48V supports 2.16 kW with a standard 45A circuit breaker.