475 Amp Cable Size at 120 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 475 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)5× 400 mm²Drop: 1.22V (2.54%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 10.06V (20.96%)
Voltage at Load46.8 VLine Loss: 579.4 W
Max Power & Breaker22.8 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1626.4 V (3388.33%)0.0 V2682.8 V (5589.17%)772540.0 WDrop High
2.5 mm²24 A18 A975.84 V (2033.0%)0.0 V1609.68 V (3353.5%)463524.0 WDrop High
4 mm²32 A25 A609.9 V (1270.62%)0.0 V1006.05 V (2095.94%)289702.5 WDrop High
6 mm²41 A32 A406.6 V (847.08%)0.0 V670.7 V (1397.29%)193135.0 WDrop High
10 mm²57 A44 A243.96 V (508.25%)0.0 V402.42 V (838.37%)115881.0 WDrop High
16 mm²76 A59 A152.47 V (317.66%)0.0 V251.51 V (523.98%)72425.6 WDrop High
25 mm²101 A78 A97.58 V (203.3%)0.0 V160.97 V (335.35%)46352.4 WDrop High
35 mm²125 A97 A69.7 V (145.21%)0.0 V114.98 V (239.54%)33108.9 WDrop High
50 mm²151 A118 A48.79 V (101.65%)0.0 V80.48 V (167.67%)23176.2 WDrop High
70 mm²192 A150 A34.85 V (72.61%)13.1 V57.49 V (119.77%)16554.4 WDrop High
95 mm²232 A181 A25.68 V (53.5%)22.3 V42.36 V (88.25%)12198.0 WDrop High
120 mm²269 A210 A20.33 V (42.35%)27.7 V33.53 V (69.86%)9656.8 WDrop High
150 mm²309 A241 A16.26 V (33.88%)31.7 V26.83 V (55.89%)7725.4 WDrop High
185 mm²353 A275 A13.19 V (27.47%)34.8 V21.75 V (45.32%)6263.8 WDrop High
240 mm²415 A324 A10.16 V (21.18%)37.8 V16.77 V (34.93%)4828.4 WDrop High
300 mm²477 A372 A8.13 V (16.94%)39.9 V13.41 V (27.95%)3862.7 WDrop High
400 mm²570 A445 A6.1 V (12.71%)41.9 V10.06 V (20.96%)2897.0 WDrop High

FAQ — 475 Amp Cable Size at 120 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 475A at 120 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 5× 400 mm² copper cable for 475A over 120m at 48V (voltage drop: 1.22V or 2.54%).

What is the power capacity of 475A at 48V?

At unity power factor, 475A at 48V supports 22.8 kW with a standard 500A circuit breaker.