⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

475 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 475 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 20.54V (2.98%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 25.41V (3.68%)
Voltage at Load669.5 VLine Loss: 16899.3 W
Max Power & Breaker567.68 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4108.14 V (595.38%)0.0 V6776.5 V (982.1%)3379862.5 WDrop High
2.5 mm²24 A18 A2464.88 V (357.23%)0.0 V4065.9 V (589.26%)2027917.5 WDrop High
4 mm²32 A25 A1540.55 V (223.27%)0.0 V2541.19 V (368.29%)1267448.4 WDrop High
6 mm²41 A32 A1027.03 V (148.85%)0.0 V1694.13 V (245.53%)844965.6 WDrop High
10 mm²57 A44 A616.22 V (89.31%)73.8 V1016.48 V (147.32%)506979.4 WDrop High
16 mm²76 A59 A385.14 V (55.82%)304.9 V635.3 V (92.07%)316862.1 WDrop High
25 mm²101 A78 A246.49 V (35.72%)443.5 V406.59 V (58.93%)202791.7 WDrop High
35 mm²125 A97 A176.06 V (25.52%)513.9 V290.42 V (42.09%)144851.2 WDrop High
50 mm²151 A118 A123.24 V (17.86%)566.8 V203.3 V (29.46%)101395.9 WDrop High
70 mm²192 A150 A88.03 V (12.76%)602.0 V145.21 V (21.05%)72425.6 WDrop High
95 mm²232 A181 A64.87 V (9.4%)625.1 V107.0 V (15.51%)53366.2 WDrop High
120 mm²269 A210 A51.35 V (7.44%)638.6 V84.71 V (12.28%)42248.3 WDrop High
150 mm²309 A241 A41.08 V (5.95%)648.9 V67.77 V (9.82%)33798.6 WDrop High
185 mm²353 A275 A33.31 V (4.83%)656.7 V54.94 V (7.96%)27404.3 WDrop High
240 mm²415 A324 A25.68 V (3.72%)664.3 V42.35 V (6.14%)21124.1 WDrop High
300 mm²477 A372 A20.54 V (2.98%)669.5 V33.88 V (4.91%)16899.3 W✓ OK (≤3%)
400 mm²570 A445 A15.41 V (2.23%)674.6 V25.41 V (3.68%)12674.5 W✓ OK (≤3%)

FAQ — 475 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 475A at 350 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 475A over 350m at 690V (voltage drop: 20.54V or 2.98%).

What is the power capacity of 475A at 690V?

At unity power factor, 475A at 690V supports 567.68 kW with a standard 500A circuit breaker.