5 Amp Cable Size at 150 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)2.5 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 11.46V (2.87%)
Voltage at Load388.9 VLine Loss: 96.3 W
Max Power & Breaker3.46 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A18.53 V (4.63%)381.5 V30.57 V (7.64%)160.5 W~ ≤5%
2.5 mm²24 A18 A11.12 V (2.78%)388.9 V18.34 V (4.59%)96.3 W✓ OK (≤3%)
4 mm²32 A25 A6.95 V (1.74%)393.1 V11.46 V (2.87%)60.2 W✓ OK (≤3%)
6 mm²41 A32 A4.63 V (1.16%)395.4 V7.64 V (1.91%)40.1 W✓ OK (≤3%)
10 mm²57 A44 A2.78 V (0.69%)397.2 V4.59 V (1.15%)24.1 W✓ OK (≤3%)
16 mm²76 A59 A1.74 V (0.43%)398.3 V2.87 V (0.72%)15.0 W✓ OK (≤3%)
25 mm²101 A78 A1.11 V (0.28%)398.9 V1.83 V (0.46%)9.6 W✓ OK (≤3%)
35 mm²125 A97 A0.79 V (0.2%)399.2 V1.31 V (0.33%)6.9 W✓ OK (≤3%)
50 mm²151 A118 A0.56 V (0.14%)399.4 V0.92 V (0.23%)4.8 W✓ OK (≤3%)
70 mm²192 A150 A0.4 V (0.1%)399.6 V0.66 V (0.16%)3.4 W✓ OK (≤3%)
95 mm²232 A181 A0.29 V (0.07%)399.7 V0.48 V (0.12%)2.5 W✓ OK (≤3%)
120 mm²269 A210 A0.23 V (0.06%)399.8 V0.38 V (0.1%)2.0 W✓ OK (≤3%)
150 mm²309 A241 A0.19 V (0.05%)399.8 V0.31 V (0.08%)1.6 W✓ OK (≤3%)
185 mm²353 A275 A0.15 V (0.04%)399.8 V0.25 V (0.06%)1.3 W✓ OK (≤3%)
240 mm²415 A324 A0.12 V (0.03%)399.9 V0.19 V (0.05%)1.0 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.02%)399.9 V0.15 V (0.04%)0.8 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.02%)399.9 V0.11 V (0.03%)0.6 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 150 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 5A at 150 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2.5 mm² copper cable for 5A over 150m at 400V (voltage drop: 11.12V or 2.78%).

What is the power capacity of 5A at 400V?

At unity power factor, 5A at 400V supports 3.46 kW with a standard 6A circuit breaker.