5 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)1.5 mm²Drop: 18.53V (2.69%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 18.34V (2.66%)
Voltage at Load671.5 VLine Loss: 160.5 W
Max Power & Breaker5.98 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A18.53 V (2.69%)671.5 V30.57 V (4.43%)160.5 W✓ OK (≤3%)
2.5 mm²24 A18 A11.12 V (1.61%)678.9 V18.34 V (2.66%)96.3 W✓ OK (≤3%)
4 mm²32 A25 A6.95 V (1.01%)683.1 V11.46 V (1.66%)60.2 W✓ OK (≤3%)
6 mm²41 A32 A4.63 V (0.67%)685.4 V7.64 V (1.11%)40.1 W✓ OK (≤3%)
10 mm²57 A44 A2.78 V (0.4%)687.2 V4.59 V (0.66%)24.1 W✓ OK (≤3%)
16 mm²76 A59 A1.74 V (0.25%)688.3 V2.87 V (0.42%)15.0 W✓ OK (≤3%)
25 mm²101 A78 A1.11 V (0.16%)688.9 V1.83 V (0.27%)9.6 W✓ OK (≤3%)
35 mm²125 A97 A0.79 V (0.12%)689.2 V1.31 V (0.19%)6.9 W✓ OK (≤3%)
50 mm²151 A118 A0.56 V (0.08%)689.4 V0.92 V (0.13%)4.8 W✓ OK (≤3%)
70 mm²192 A150 A0.4 V (0.06%)689.6 V0.66 V (0.09%)3.4 W✓ OK (≤3%)
95 mm²232 A181 A0.29 V (0.04%)689.7 V0.48 V (0.07%)2.5 W✓ OK (≤3%)
120 mm²269 A210 A0.23 V (0.03%)689.8 V0.38 V (0.06%)2.0 W✓ OK (≤3%)
150 mm²309 A241 A0.19 V (0.03%)689.8 V0.31 V (0.04%)1.6 W✓ OK (≤3%)
185 mm²353 A275 A0.15 V (0.02%)689.8 V0.25 V (0.04%)1.3 W✓ OK (≤3%)
240 mm²415 A324 A0.12 V (0.02%)689.9 V0.19 V (0.03%)1.0 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.01%)689.9 V0.15 V (0.02%)0.8 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.01%)689.9 V0.11 V (0.02%)0.6 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 5A at 150 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 5A over 150m at 690V (voltage drop: 18.53V or 2.69%).

What is the power capacity of 5A at 690V?

At unity power factor, 5A at 690V supports 5.98 kW with a standard 6A circuit breaker.