500 Amp Cable Size at 350 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 500 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 8.11V (2.02%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 26.75V (6.69%)
Voltage at Load391.9 VLine Loss: 7021.9 W
Max Power & Breaker346.41 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4324.35 V (1081.09%)0.0 V7133.16 V (1783.29%)3745000.0 WDrop High
2.5 mm²24 A18 A2594.61 V (648.65%)0.0 V4279.9 V (1069.97%)2247000.0 WDrop High
4 mm²32 A25 A1621.63 V (405.41%)0.0 V2674.94 V (668.73%)1404375.0 WDrop High
6 mm²41 A32 A1081.09 V (270.27%)0.0 V1783.29 V (445.82%)936250.0 WDrop High
10 mm²57 A44 A648.65 V (162.16%)0.0 V1069.97 V (267.49%)561750.0 WDrop High
16 mm²76 A59 A405.41 V (101.35%)0.0 V668.73 V (167.18%)351093.7 WDrop High
25 mm²101 A78 A259.46 V (64.87%)140.5 V427.99 V (107.0%)224700.0 WDrop High
35 mm²125 A97 A185.33 V (46.33%)214.7 V305.71 V (76.43%)160500.0 WDrop High
50 mm²151 A118 A129.73 V (32.43%)270.3 V213.99 V (53.5%)112350.0 WDrop High
70 mm²192 A150 A92.66 V (23.17%)307.3 V152.85 V (38.21%)80250.0 WDrop High
95 mm²232 A181 A68.28 V (17.07%)331.7 V112.63 V (28.16%)59131.6 WDrop High
120 mm²269 A210 A54.05 V (13.51%)345.9 V89.16 V (22.29%)46812.5 WDrop High
150 mm²309 A241 A43.24 V (10.81%)356.8 V71.33 V (17.83%)37450.0 WDrop High
185 mm²353 A275 A35.06 V (8.77%)364.9 V57.84 V (14.46%)30364.9 WDrop High
240 mm²415 A324 A27.03 V (6.76%)373.0 V44.58 V (11.15%)23406.2 WDrop High
300 mm²477 A372 A21.62 V (5.41%)378.4 V35.67 V (8.92%)18725.0 WDrop High
400 mm²570 A445 A16.22 V (4.05%)383.8 V26.75 V (6.69%)14043.7 W~ ≤5%

FAQ — 500 Amp Cable Size at 350 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 500A at 350 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 500A over 350m at 400V (voltage drop: 8.11V or 2.02%).

What is the power capacity of 500A at 400V?

At unity power factor, 500A at 400V supports 346.41 kW with a standard 500A circuit breaker.