500 Amp Cable Size at 500 Meters (690V Three-Phase (Wind / Heavy Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 500 A over 500 m (1640.4 ft).
Copper Cable (≤3% Drop)2× 400 mm²Drop: 11.59V (1.68%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 38.21V (5.54%)
Voltage at Load678.4 VLine Loss: 10031.2 W
Max Power & Breaker597.56 kW500A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 500m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 6177.65 V (895.31%) | 0.0 V | 10190.23 V (1476.85%) | 5350000.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 3706.59 V (537.19%) | 0.0 V | 6114.14 V (886.11%) | 3210000.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 2316.62 V (335.74%) | 0.0 V | 3821.34 V (553.82%) | 2006250.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 1544.41 V (223.83%) | 0.0 V | 2547.56 V (369.21%) | 1337500.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 926.65 V (134.3%) | 0.0 V | 1528.53 V (221.53%) | 802500.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 579.15 V (83.94%) | 110.8 V | 955.33 V (138.45%) | 501562.5 W | Drop High |
| 25 mm² | 101 A | 78 A | 370.66 V (53.72%) | 319.3 V | 611.41 V (88.61%) | 321000.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 264.76 V (38.37%) | 425.2 V | 436.72 V (63.29%) | 229285.7 W | Drop High |
| 50 mm² | 151 A | 118 A | 185.33 V (26.86%) | 504.7 V | 305.71 V (44.31%) | 160500.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 132.38 V (19.19%) | 557.6 V | 218.36 V (31.65%) | 114642.9 W | Drop High |
| 95 mm² | 232 A | 181 A | 97.54 V (14.14%) | 592.5 V | 160.9 V (23.32%) | 84473.7 W | Drop High |
| 120 mm² | 269 A | 210 A | 77.22 V (11.19%) | 612.8 V | 127.38 V (18.46%) | 66875.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 61.78 V (8.95%) | 628.2 V | 101.9 V (14.77%) | 53500.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 50.09 V (7.26%) | 639.9 V | 82.62 V (11.97%) | 43378.4 W | Drop High |
| 240 mm² | 415 A | 324 A | 38.61 V (5.6%) | 651.4 V | 63.69 V (9.23%) | 33437.5 W | Drop High |
| 300 mm² | 477 A | 372 A | 30.89 V (4.48%) | 659.1 V | 50.95 V (7.38%) | 26750.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 23.17 V (3.36%) | 666.8 V | 38.21 V (5.54%) | 20062.5 W | ~ ≤5% |
FAQ — 500 Amp Cable Size at 500 Meters (690V Three-Phase (Wind / Heavy Industrial))
What mm² cable size is required for 500A at 500 meters (690V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 500A over 500m at 690V (voltage drop: 11.59V or 1.68%).
What is the power capacity of 500A at 690V?
At unity power factor, 500A at 690V supports 597.56 kW with a standard 500A circuit breaker.
Related Lengths & Currents (690V)
500A · 5m (690V)500A · 10m (690V)500A · 15m (690V)500A · 20m (690V)500A · 25m (690V)500A · 30m (690V)500A · 35m (690V)500A · 40m (690V)500A · 45m (690V)500A · 50m (690V)500A · 60m (690V)500A · 70m (690V)10A · 500m (690V)16A · 500m (690V)20A · 500m (690V)25A · 500m (690V)32A · 500m (690V)40A · 500m (690V)50A · 500m (690V)63A · 500m (690V)80A · 500m (690V)100A · 500m (690V)125A · 500m (690V)160A · 500m (690V)200A · 500m (690V)