20 Amp Cable Size at 500 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 20 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 14.83V (2.15%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 17.47V (2.53%)
Voltage at Load675.2 VLine Loss: 513.6 W
Max Power & Breaker23.9 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A247.11 V (35.81%)442.9 V407.61 V (59.07%)8560.0 WDrop High
2.5 mm²24 A18 A148.26 V (21.49%)541.7 V244.57 V (35.44%)5136.0 WDrop High
4 mm²32 A25 A92.66 V (13.43%)597.3 V152.85 V (22.15%)3210.0 WDrop High
6 mm²41 A32 A61.78 V (8.95%)628.2 V101.9 V (14.77%)2140.0 WDrop High
10 mm²57 A44 A37.07 V (5.37%)652.9 V61.14 V (8.86%)1284.0 WDrop High
16 mm²76 A59 A23.17 V (3.36%)666.8 V38.21 V (5.54%)802.5 W~ ≤5%
25 mm²101 A78 A14.83 V (2.15%)675.2 V24.46 V (3.54%)513.6 W✓ OK (≤3%)
35 mm²125 A97 A10.59 V (1.53%)679.4 V17.47 V (2.53%)366.9 W✓ OK (≤3%)
50 mm²151 A118 A7.41 V (1.07%)682.6 V12.23 V (1.77%)256.8 W✓ OK (≤3%)
70 mm²192 A150 A5.3 V (0.77%)684.7 V8.73 V (1.27%)183.4 W✓ OK (≤3%)
95 mm²232 A181 A3.9 V (0.57%)686.1 V6.44 V (0.93%)135.2 W✓ OK (≤3%)
120 mm²269 A210 A3.09 V (0.45%)686.9 V5.1 V (0.74%)107.0 W✓ OK (≤3%)
150 mm²309 A241 A2.47 V (0.36%)687.5 V4.08 V (0.59%)85.6 W✓ OK (≤3%)
185 mm²353 A275 A2.0 V (0.29%)688.0 V3.3 V (0.48%)69.4 W✓ OK (≤3%)
240 mm²415 A324 A1.54 V (0.22%)688.5 V2.55 V (0.37%)53.5 W✓ OK (≤3%)
300 mm²477 A372 A1.24 V (0.18%)688.8 V2.04 V (0.3%)42.8 W✓ OK (≤3%)
400 mm²570 A445 A0.93 V (0.13%)689.1 V1.53 V (0.22%)32.1 W✓ OK (≤3%)

FAQ — 20 Amp Cable Size at 500 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 20A at 500 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 20A over 500m at 690V (voltage drop: 14.83V or 2.15%).

What is the power capacity of 20A at 690V?

At unity power factor, 20A at 690V supports 23.9 kW with a standard 20A circuit breaker.