100 Amp Cable Size at 500 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 100 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 19.51V (2.83%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 20.38V (2.95%)
Voltage at Load670.5 VLine Loss: 3378.9 W
Max Power & Breaker119.51 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1235.53 V (179.06%)0.0 V2038.05 V (295.37%)214000.0 WDrop High
2.5 mm²24 A18 A741.32 V (107.44%)0.0 V1222.83 V (177.22%)128400.0 WDrop High
4 mm²32 A25 A463.32 V (67.15%)226.7 V764.27 V (110.76%)80250.0 WDrop High
6 mm²41 A32 A308.88 V (44.77%)381.1 V509.51 V (73.84%)53500.0 WDrop High
10 mm²57 A44 A185.33 V (26.86%)504.7 V305.71 V (44.31%)32100.0 WDrop High
16 mm²76 A59 A115.83 V (16.79%)574.2 V191.07 V (27.69%)20062.5 WDrop High
25 mm²101 A78 A74.13 V (10.74%)615.9 V122.28 V (17.72%)12840.0 WDrop High
35 mm²125 A97 A52.95 V (7.67%)637.0 V87.34 V (12.66%)9171.4 WDrop High
50 mm²151 A118 A37.07 V (5.37%)652.9 V61.14 V (8.86%)6420.0 WDrop High
70 mm²192 A150 A26.48 V (3.84%)663.5 V43.67 V (6.33%)4585.7 W~ ≤5%
95 mm²232 A181 A19.51 V (2.83%)670.5 V32.18 V (4.66%)3378.9 W✓ OK (≤3%)
120 mm²269 A210 A15.44 V (2.24%)674.6 V25.48 V (3.69%)2675.0 W✓ OK (≤3%)
150 mm²309 A241 A12.36 V (1.79%)677.6 V20.38 V (2.95%)2140.0 W✓ OK (≤3%)
185 mm²353 A275 A10.02 V (1.45%)680.0 V16.52 V (2.39%)1735.1 W✓ OK (≤3%)
240 mm²415 A324 A7.72 V (1.12%)682.3 V12.74 V (1.85%)1337.5 W✓ OK (≤3%)
300 mm²477 A372 A6.18 V (0.9%)683.8 V10.19 V (1.48%)1070.0 W✓ OK (≤3%)
400 mm²570 A445 A4.63 V (0.67%)685.4 V7.64 V (1.11%)802.5 W✓ OK (≤3%)

FAQ — 100 Amp Cable Size at 500 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 100A at 500 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 100A over 500m at 690V (voltage drop: 19.51V or 2.83%).

What is the power capacity of 100A at 690V?

At unity power factor, 100A at 690V supports 119.51 kW with a standard 100A circuit breaker.