550 Amp Cable Size at 150 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)7× 400 mm²Drop: 1.26V (2.63%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 14.56V (30.34%)
Voltage at Load46.7 VLine Loss: 693.6 W
Max Power & Breaker26.4 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2354.0 V (4904.17%)0.0 V3883.0 V (8089.58%)1294700.0 WDrop High
2.5 mm²24 A18 A1412.4 V (2942.5%)0.0 V2329.8 V (4853.75%)776820.0 WDrop High
4 mm²32 A25 A882.75 V (1839.06%)0.0 V1456.12 V (3033.59%)485512.5 WDrop High
6 mm²41 A32 A588.5 V (1226.04%)0.0 V970.75 V (2022.4%)323675.0 WDrop High
10 mm²57 A44 A353.1 V (735.62%)0.0 V582.45 V (1213.44%)194205.0 WDrop High
16 mm²76 A59 A220.69 V (459.77%)0.0 V364.03 V (758.4%)121378.1 WDrop High
25 mm²101 A78 A141.24 V (294.25%)0.0 V232.98 V (485.38%)77682.0 WDrop High
35 mm²125 A97 A100.89 V (210.18%)0.0 V166.41 V (346.7%)55487.1 WDrop High
50 mm²151 A118 A70.62 V (147.12%)0.0 V116.49 V (242.69%)38841.0 WDrop High
70 mm²192 A150 A50.44 V (105.09%)0.0 V83.21 V (173.35%)27743.6 WDrop High
95 mm²232 A181 A37.17 V (77.43%)10.8 V61.31 V (127.73%)20442.6 WDrop High
120 mm²269 A210 A29.43 V (61.3%)18.6 V48.54 V (101.12%)16183.8 WDrop High
150 mm²309 A241 A23.54 V (49.04%)24.5 V38.83 V (80.9%)12947.0 WDrop High
185 mm²353 A275 A19.09 V (39.76%)28.9 V31.48 V (65.59%)10497.6 WDrop High
240 mm²415 A324 A14.71 V (30.65%)33.3 V24.27 V (50.56%)8091.9 WDrop High
300 mm²477 A372 A11.77 V (24.52%)36.2 V19.41 V (40.45%)6473.5 WDrop High
400 mm²570 A445 A8.83 V (18.39%)39.2 V14.56 V (30.34%)4855.1 WDrop High

FAQ — 550 Amp Cable Size at 150 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 550A at 150 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 7× 400 mm² copper cable for 550A over 150m at 48V (voltage drop: 1.26V or 2.63%).

What is the power capacity of 550A at 48V?

At unity power factor, 550A at 48V supports 26.4 kW with a standard 600A circuit breaker.