⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

550 Amp Cable Size at 5 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 0.29V (0.61%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.49V (1.01%)
Voltage at Load47.7 VLine Loss: 161.8 W
Max Power & Breaker26.4 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A78.47 V (163.47%)0.0 V129.43 V (269.65%)43156.7 WDrop High
2.5 mm²24 A18 A47.08 V (98.08%)0.9 V77.66 V (161.79%)25894.0 WDrop High
4 mm²32 A25 A29.43 V (61.3%)18.6 V48.54 V (101.12%)16183.8 WDrop High
6 mm²41 A32 A19.62 V (40.87%)28.4 V32.36 V (67.41%)10789.2 WDrop High
10 mm²57 A44 A11.77 V (24.52%)36.2 V19.41 V (40.45%)6473.5 WDrop High
16 mm²76 A59 A7.36 V (15.33%)40.6 V12.13 V (25.28%)4045.9 WDrop High
25 mm²101 A78 A4.71 V (9.81%)43.3 V7.77 V (16.18%)2589.4 WDrop High
35 mm²125 A97 A3.36 V (7.01%)44.6 V5.55 V (11.56%)1849.6 WDrop High
50 mm²151 A118 A2.35 V (4.9%)45.6 V3.88 V (8.09%)1294.7 WDrop High
70 mm²192 A150 A1.68 V (3.5%)46.3 V2.77 V (5.78%)924.8 WDrop High
95 mm²232 A181 A1.24 V (2.58%)46.8 V2.04 V (4.26%)681.4 WDrop High
120 mm²269 A210 A0.98 V (2.04%)47.0 V1.62 V (3.37%)539.5 WDrop High
150 mm²309 A241 A0.78 V (1.63%)47.2 V1.29 V (2.7%)431.6 WDrop High
185 mm²353 A275 A0.64 V (1.33%)47.4 V1.05 V (2.19%)349.9 WDrop High
240 mm²415 A324 A0.49 V (1.02%)47.5 V0.81 V (1.69%)269.7 WDrop High
300 mm²477 A372 A0.39 V (0.82%)47.6 V0.65 V (1.35%)215.8 WDrop High
400 mm²570 A445 A0.29 V (0.61%)47.7 V0.49 V (1.01%)161.8 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 5 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 550A at 5 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 5m at 48V (voltage drop: 0.29V or 0.61%).

What is the power capacity of 550A at 48V?

At unity power factor, 550A at 48V supports 26.4 kW with a standard 600A circuit breaker.