550 Amp Cable Size at 25 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 1.27V (0.32%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.1V (0.53%)
Voltage at Load398.7 VLine Loss: 1213.8 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A339.77 V (84.94%)60.2 V560.46 V (140.12%)323675.0 WDrop High
2.5 mm²24 A18 A203.86 V (50.97%)196.1 V336.28 V (84.07%)194205.0 WDrop High
4 mm²32 A25 A127.41 V (31.85%)272.6 V210.17 V (52.54%)121378.1 WDrop High
6 mm²41 A32 A84.94 V (21.24%)315.1 V140.12 V (35.03%)80918.7 WDrop High
10 mm²57 A44 A50.97 V (12.74%)349.0 V84.07 V (21.02%)48551.2 WDrop High
16 mm²76 A59 A31.85 V (7.96%)368.1 V52.54 V (13.14%)30344.5 WDrop High
25 mm²101 A78 A20.39 V (5.1%)379.6 V33.63 V (8.41%)19420.5 WDrop High
35 mm²125 A97 A14.56 V (3.64%)385.4 V24.02 V (6.0%)13871.8 WDrop High
50 mm²151 A118 A10.19 V (2.55%)389.8 V16.81 V (4.2%)9710.2 WDrop High
70 mm²192 A150 A7.28 V (1.82%)392.7 V12.01 V (3.0%)6935.9 WDrop High
95 mm²232 A181 A5.36 V (1.34%)394.6 V8.85 V (2.21%)5110.7 WDrop High
120 mm²269 A210 A4.25 V (1.06%)395.8 V7.01 V (1.75%)4045.9 WDrop High
150 mm²309 A241 A3.4 V (0.85%)396.6 V5.6 V (1.4%)3236.7 WDrop High
185 mm²353 A275 A2.75 V (0.69%)397.2 V4.54 V (1.14%)2624.4 WDrop High
240 mm²415 A324 A2.12 V (0.53%)397.9 V3.5 V (0.88%)2023.0 WDrop High
300 mm²477 A372 A1.7 V (0.42%)398.3 V2.8 V (0.7%)1618.4 WDrop High
400 mm²570 A445 A1.27 V (0.32%)398.7 V2.1 V (0.53%)1213.8 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 25 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 550A at 25 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 25m at 400V (voltage drop: 1.27V or 0.32%).

What is the power capacity of 550A at 400V?

At unity power factor, 550A at 400V supports 381.05 kW with a standard 600A circuit breaker.