⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

550 Amp Cable Size at 50 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 2.55V (0.64%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.2V (1.05%)
Voltage at Load397.5 VLine Loss: 2427.6 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A679.54 V (169.89%)0.0 V1120.93 V (280.23%)647350.0 WDrop High
2.5 mm²24 A18 A407.72 V (101.93%)0.0 V672.56 V (168.14%)388410.0 WDrop High
4 mm²32 A25 A254.83 V (63.71%)145.2 V420.35 V (105.09%)242756.2 WDrop High
6 mm²41 A32 A169.89 V (42.47%)230.1 V280.23 V (70.06%)161837.5 WDrop High
10 mm²57 A44 A101.93 V (25.48%)298.1 V168.14 V (42.03%)97102.5 WDrop High
16 mm²76 A59 A63.71 V (15.93%)336.3 V105.09 V (26.27%)60689.1 WDrop High
25 mm²101 A78 A40.77 V (10.19%)359.2 V67.26 V (16.81%)38841.0 WDrop High
35 mm²125 A97 A29.12 V (7.28%)370.9 V48.04 V (12.01%)27743.6 WDrop High
50 mm²151 A118 A20.39 V (5.1%)379.6 V33.63 V (8.41%)19420.5 WDrop High
70 mm²192 A150 A14.56 V (3.64%)385.4 V24.02 V (6.0%)13871.8 WDrop High
95 mm²232 A181 A10.73 V (2.68%)389.3 V17.7 V (4.42%)10221.3 WDrop High
120 mm²269 A210 A8.49 V (2.12%)391.5 V14.01 V (3.5%)8091.9 WDrop High
150 mm²309 A241 A6.8 V (1.7%)393.2 V11.21 V (2.8%)6473.5 WDrop High
185 mm²353 A275 A5.51 V (1.38%)394.5 V9.09 V (2.27%)5248.8 WDrop High
240 mm²415 A324 A4.25 V (1.06%)395.8 V7.01 V (1.75%)4045.9 WDrop High
300 mm²477 A372 A3.4 V (0.85%)396.6 V5.6 V (1.4%)3236.7 WDrop High
400 mm²570 A445 A2.55 V (0.64%)397.5 V4.2 V (1.05%)2427.6 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 50 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 550A at 50 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 50m at 400V (voltage drop: 2.55V or 0.64%).

What is the power capacity of 550A at 400V?

At unity power factor, 550A at 400V supports 381.05 kW with a standard 600A circuit breaker.