550 Amp Cable Size at 40 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 2.04V (0.51%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.36V (0.84%)
Voltage at Load398.0 VLine Loss: 1942.0 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A543.63 V (135.91%)0.0 V896.74 V (224.19%)517880.0 WDrop High
2.5 mm²24 A18 A326.18 V (81.54%)73.8 V538.04 V (134.51%)310728.0 WDrop High
4 mm²32 A25 A203.86 V (50.97%)196.1 V336.28 V (84.07%)194205.0 WDrop High
6 mm²41 A32 A135.91 V (33.98%)264.1 V224.19 V (56.05%)129470.0 WDrop High
10 mm²57 A44 A81.54 V (20.39%)318.5 V134.51 V (33.63%)77682.0 WDrop High
16 mm²76 A59 A50.97 V (12.74%)349.0 V84.07 V (21.02%)48551.2 WDrop High
25 mm²101 A78 A32.62 V (8.15%)367.4 V53.8 V (13.45%)31072.8 WDrop High
35 mm²125 A97 A23.3 V (5.82%)376.7 V38.43 V (9.61%)22194.9 WDrop High
50 mm²151 A118 A16.31 V (4.08%)383.7 V26.9 V (6.73%)15536.4 WDrop High
70 mm²192 A150 A11.65 V (2.91%)388.4 V19.22 V (4.8%)11097.4 WDrop High
95 mm²232 A181 A8.58 V (2.15%)391.4 V14.16 V (3.54%)8177.1 WDrop High
120 mm²269 A210 A6.8 V (1.7%)393.2 V11.21 V (2.8%)6473.5 WDrop High
150 mm²309 A241 A5.44 V (1.36%)394.6 V8.97 V (2.24%)5178.8 WDrop High
185 mm²353 A275 A4.41 V (1.1%)395.6 V7.27 V (1.82%)4199.0 WDrop High
240 mm²415 A324 A3.4 V (0.85%)396.6 V5.6 V (1.4%)3236.8 WDrop High
300 mm²477 A372 A2.72 V (0.68%)397.3 V4.48 V (1.12%)2589.4 WDrop High
400 mm²570 A445 A2.04 V (0.51%)398.0 V3.36 V (0.84%)1942.0 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 40 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 550A at 40 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 40m at 400V (voltage drop: 2.04V or 0.51%).

What is the power capacity of 550A at 400V?

At unity power factor, 550A at 400V supports 381.05 kW with a standard 600A circuit breaker.