550 Amp Cable Size at 300 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)13× 400 mm²Drop: 1.36V (2.83%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 29.12V (60.67%)
Voltage at Load46.6 VLine Loss: 746.9 W
Max Power & Breaker26.4 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4708.0 V (9808.33%)0.0 V7766.0 V (16179.17%)2589400.0 WDrop High
2.5 mm²24 A18 A2824.8 V (5885.0%)0.0 V4659.6 V (9707.5%)1553640.0 WDrop High
4 mm²32 A25 A1765.5 V (3678.12%)0.0 V2912.25 V (6067.19%)971025.0 WDrop High
6 mm²41 A32 A1177.0 V (2452.08%)0.0 V1941.5 V (4044.79%)647350.0 WDrop High
10 mm²57 A44 A706.2 V (1471.25%)0.0 V1164.9 V (2426.87%)388410.0 WDrop High
16 mm²76 A59 A441.38 V (919.53%)0.0 V728.06 V (1516.8%)242756.2 WDrop High
25 mm²101 A78 A282.48 V (588.5%)0.0 V465.96 V (970.75%)155364.0 WDrop High
35 mm²125 A97 A201.77 V (420.36%)0.0 V332.83 V (693.39%)110974.3 WDrop High
50 mm²151 A118 A141.24 V (294.25%)0.0 V232.98 V (485.38%)77682.0 WDrop High
70 mm²192 A150 A100.89 V (210.18%)0.0 V166.41 V (346.7%)55487.1 WDrop High
95 mm²232 A181 A74.34 V (154.87%)0.0 V122.62 V (255.46%)40885.3 WDrop High
120 mm²269 A210 A58.85 V (122.6%)0.0 V97.07 V (202.24%)32367.5 WDrop High
150 mm²309 A241 A47.08 V (98.08%)0.9 V77.66 V (161.79%)25894.0 WDrop High
185 mm²353 A275 A38.17 V (79.53%)9.8 V62.97 V (131.18%)20995.1 WDrop High
240 mm²415 A324 A29.43 V (61.3%)18.6 V48.54 V (101.12%)16183.8 WDrop High
300 mm²477 A372 A23.54 V (49.04%)24.5 V38.83 V (80.9%)12947.0 WDrop High
400 mm²570 A445 A17.65 V (36.78%)30.3 V29.12 V (60.67%)9710.2 WDrop High

FAQ — 550 Amp Cable Size at 300 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 550A at 300 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 13× 400 mm² copper cable for 550A over 300m at 48V (voltage drop: 1.36V or 2.83%).

What is the power capacity of 550A at 48V?

At unity power factor, 550A at 48V supports 26.4 kW with a standard 600A circuit breaker.