550 Amp Cable Size at 35 Meters (690V Three-Phase (Wind / Heavy Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 35 m (114.8 ft).
Copper Cable (≤3% Drop)400 mm²Drop: 1.78V (0.26%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.94V (0.43%)
Voltage at Load688.2 VLine Loss: 1699.3 W
Max Power & Breaker657.31 kW600A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 475.68 V (68.94%) | 214.3 V | 784.65 V (113.72%) | 453145.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 285.41 V (41.36%) | 404.6 V | 470.79 V (68.23%) | 271887.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 178.38 V (25.85%) | 511.6 V | 294.24 V (42.64%) | 169929.4 W | Drop High |
| 6 mm² | 41 A | 32 A | 118.92 V (17.23%) | 571.1 V | 196.16 V (28.43%) | 113286.2 W | Drop High |
| 10 mm² | 57 A | 44 A | 71.35 V (10.34%) | 618.6 V | 117.7 V (17.06%) | 67971.8 W | Drop High |
| 16 mm² | 76 A | 59 A | 44.59 V (6.46%) | 645.4 V | 73.56 V (10.66%) | 42482.3 W | Drop High |
| 25 mm² | 101 A | 78 A | 28.54 V (4.14%) | 661.5 V | 47.08 V (6.82%) | 27188.7 W | Drop High |
| 35 mm² | 125 A | 97 A | 20.39 V (2.95%) | 669.6 V | 33.63 V (4.87%) | 19420.5 W | Drop High |
| 50 mm² | 151 A | 118 A | 14.27 V (2.07%) | 675.7 V | 23.54 V (3.41%) | 13594.4 W | Drop High |
| 70 mm² | 192 A | 150 A | 10.19 V (1.48%) | 679.8 V | 16.81 V (2.44%) | 9710.2 W | Drop High |
| 95 mm² | 232 A | 181 A | 7.51 V (1.09%) | 682.5 V | 12.39 V (1.8%) | 7154.9 W | Drop High |
| 120 mm² | 269 A | 210 A | 5.95 V (0.86%) | 684.1 V | 9.81 V (1.42%) | 5664.3 W | Drop High |
| 150 mm² | 309 A | 241 A | 4.76 V (0.69%) | 685.2 V | 7.85 V (1.14%) | 4531.4 W | Drop High |
| 185 mm² | 353 A | 275 A | 3.86 V (0.56%) | 686.1 V | 6.36 V (0.92%) | 3674.1 W | Drop High |
| 240 mm² | 415 A | 324 A | 2.97 V (0.43%) | 687.0 V | 4.9 V (0.71%) | 2832.2 W | Drop High |
| 300 mm² | 477 A | 372 A | 2.38 V (0.34%) | 687.6 V | 3.92 V (0.57%) | 2265.7 W | Drop High |
| 400 mm² | 570 A | 445 A | 1.78 V (0.26%) | 688.2 V | 2.94 V (0.43%) | 1699.3 W | ✓ OK (≤3%) |
FAQ — 550 Amp Cable Size at 35 Meters (690V Three-Phase (Wind / Heavy Industrial))
What mm² cable size is required for 550A at 35 meters (690V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 35m at 690V (voltage drop: 1.78V or 0.26%).
What is the power capacity of 550A at 690V?
At unity power factor, 550A at 690V supports 657.31 kW with a standard 600A circuit breaker.
Related Lengths & Currents (690V)
550A · 5m (690V)550A · 10m (690V)550A · 15m (690V)550A · 20m (690V)550A · 25m (690V)550A · 30m (690V)550A · 40m (690V)550A · 45m (690V)550A · 50m (690V)550A · 60m (690V)550A · 70m (690V)10A · 35m (690V)16A · 35m (690V)20A · 35m (690V)25A · 35m (690V)32A · 35m (690V)40A · 35m (690V)50A · 35m (690V)63A · 35m (690V)80A · 35m (690V)100A · 35m (690V)125A · 35m (690V)160A · 35m (690V)200A · 35m (690V)