550 Amp Cable Size at 40 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 2.04V (0.3%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.36V (0.49%)
Voltage at Load688.0 VLine Loss: 1942.0 W
Max Power & Breaker657.31 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A543.63 V (78.79%)146.4 V896.74 V (129.96%)517880.0 WDrop High
2.5 mm²24 A18 A326.18 V (47.27%)363.8 V538.04 V (77.98%)310728.0 WDrop High
4 mm²32 A25 A203.86 V (29.55%)486.1 V336.28 V (48.74%)194205.0 WDrop High
6 mm²41 A32 A135.91 V (19.7%)554.1 V224.19 V (32.49%)129470.0 WDrop High
10 mm²57 A44 A81.54 V (11.82%)608.5 V134.51 V (19.49%)77682.0 WDrop High
16 mm²76 A59 A50.97 V (7.39%)639.0 V84.07 V (12.18%)48551.2 WDrop High
25 mm²101 A78 A32.62 V (4.73%)657.4 V53.8 V (7.8%)31072.8 WDrop High
35 mm²125 A97 A23.3 V (3.38%)666.7 V38.43 V (5.57%)22194.9 WDrop High
50 mm²151 A118 A16.31 V (2.36%)673.7 V26.9 V (3.9%)15536.4 WDrop High
70 mm²192 A150 A11.65 V (1.69%)678.4 V19.22 V (2.78%)11097.4 WDrop High
95 mm²232 A181 A8.58 V (1.24%)681.4 V14.16 V (2.05%)8177.1 WDrop High
120 mm²269 A210 A6.8 V (0.98%)683.2 V11.21 V (1.62%)6473.5 WDrop High
150 mm²309 A241 A5.44 V (0.79%)684.6 V8.97 V (1.3%)5178.8 WDrop High
185 mm²353 A275 A4.41 V (0.64%)685.6 V7.27 V (1.05%)4199.0 WDrop High
240 mm²415 A324 A3.4 V (0.49%)686.6 V5.6 V (0.81%)3236.8 WDrop High
300 mm²477 A372 A2.72 V (0.39%)687.3 V4.48 V (0.65%)2589.4 WDrop High
400 mm²570 A445 A2.04 V (0.3%)688.0 V3.36 V (0.49%)1942.0 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 40 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 550A at 40 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 40m at 690V (voltage drop: 2.04V or 0.3%).

What is the power capacity of 550A at 690V?

At unity power factor, 550A at 690V supports 657.31 kW with a standard 600A circuit breaker.