550 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 15 m (49.2 ft).
Copper Cable (≤3% Drop)400 mm²Drop: 0.76V (0.11%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.26V (0.18%)
Voltage at Load689.2 VLine Loss: 728.3 W
Max Power & Breaker657.31 kW600A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 15m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 203.86 V (29.55%) | 486.1 V | 336.28 V (48.74%) | 194205.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 122.32 V (17.73%) | 567.7 V | 201.77 V (29.24%) | 116523.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 76.45 V (11.08%) | 613.6 V | 126.1 V (18.28%) | 72826.9 W | Drop High |
| 6 mm² | 41 A | 32 A | 50.97 V (7.39%) | 639.0 V | 84.07 V (12.18%) | 48551.2 W | Drop High |
| 10 mm² | 57 A | 44 A | 30.58 V (4.43%) | 659.4 V | 50.44 V (7.31%) | 29130.8 W | Drop High |
| 16 mm² | 76 A | 59 A | 19.11 V (2.77%) | 670.9 V | 31.53 V (4.57%) | 18206.7 W | Drop High |
| 25 mm² | 101 A | 78 A | 12.23 V (1.77%) | 677.8 V | 20.18 V (2.92%) | 11652.3 W | Drop High |
| 35 mm² | 125 A | 97 A | 8.74 V (1.27%) | 681.3 V | 14.41 V (2.09%) | 8323.1 W | Drop High |
| 50 mm² | 151 A | 118 A | 6.12 V (0.89%) | 683.9 V | 10.09 V (1.46%) | 5826.2 W | Drop High |
| 70 mm² | 192 A | 150 A | 4.37 V (0.63%) | 685.6 V | 7.21 V (1.04%) | 4161.5 W | Drop High |
| 95 mm² | 232 A | 181 A | 3.22 V (0.47%) | 686.8 V | 5.31 V (0.77%) | 3066.4 W | Drop High |
| 120 mm² | 269 A | 210 A | 2.55 V (0.37%) | 687.5 V | 4.2 V (0.61%) | 2427.6 W | Drop High |
| 150 mm² | 309 A | 241 A | 2.04 V (0.3%) | 688.0 V | 3.36 V (0.49%) | 1942.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 1.65 V (0.24%) | 688.3 V | 2.73 V (0.4%) | 1574.6 W | Drop High |
| 240 mm² | 415 A | 324 A | 1.27 V (0.18%) | 688.7 V | 2.1 V (0.3%) | 1213.8 W | Drop High |
| 300 mm² | 477 A | 372 A | 1.02 V (0.15%) | 689.0 V | 1.68 V (0.24%) | 971.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 0.76 V (0.11%) | 689.2 V | 1.26 V (0.18%) | 728.3 W | ✓ OK (≤3%) |
FAQ — 550 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))
What mm² cable size is required for 550A at 15 meters (690V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 15m at 690V (voltage drop: 0.76V or 0.11%).
What is the power capacity of 550A at 690V?
At unity power factor, 550A at 690V supports 657.31 kW with a standard 600A circuit breaker.
Related Lengths & Currents (690V)
550A · 5m (690V)550A · 10m (690V)550A · 20m (690V)550A · 25m (690V)550A · 30m (690V)550A · 35m (690V)550A · 40m (690V)550A · 45m (690V)550A · 50m (690V)550A · 60m (690V)550A · 70m (690V)10A · 15m (690V)16A · 15m (690V)20A · 15m (690V)25A · 15m (690V)32A · 15m (690V)40A · 15m (690V)50A · 15m (690V)63A · 15m (690V)80A · 15m (690V)100A · 15m (690V)125A · 15m (690V)160A · 15m (690V)200A · 15m (690V)