⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

550 Amp Cable Size at 80 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 4.71V (2.05%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.77V (3.38%)
Voltage at Load225.3 VLine Loss: 2589.4 W
Max Power & Breaker126.5 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1255.47 V (545.86%)0.0 V2070.93 V (900.41%)690506.7 WDrop High
2.5 mm²24 A18 A753.28 V (327.51%)0.0 V1242.56 V (540.24%)414304.0 WDrop High
4 mm²32 A25 A470.8 V (204.7%)0.0 V776.6 V (337.65%)258940.0 WDrop High
6 mm²41 A32 A313.87 V (136.46%)0.0 V517.73 V (225.1%)172626.7 WDrop High
10 mm²57 A44 A188.32 V (81.88%)41.7 V310.64 V (135.06%)103576.0 WDrop High
16 mm²76 A59 A117.7 V (51.17%)112.3 V194.15 V (84.41%)64735.0 WDrop High
25 mm²101 A78 A75.33 V (32.75%)154.7 V124.26 V (54.02%)41430.4 WDrop High
35 mm²125 A97 A53.81 V (23.39%)176.2 V88.75 V (38.59%)29593.1 WDrop High
50 mm²151 A118 A37.66 V (16.38%)192.3 V62.13 V (27.01%)20715.2 WDrop High
70 mm²192 A150 A26.9 V (11.7%)203.1 V44.38 V (19.29%)14796.6 WDrop High
95 mm²232 A181 A19.82 V (8.62%)210.2 V32.7 V (14.22%)10902.7 WDrop High
120 mm²269 A210 A15.69 V (6.82%)214.3 V25.89 V (11.26%)8631.3 WDrop High
150 mm²309 A241 A12.55 V (5.46%)217.4 V20.71 V (9.0%)6905.1 WDrop High
185 mm²353 A275 A10.18 V (4.43%)219.8 V16.79 V (7.3%)5598.7 WDrop High
240 mm²415 A324 A7.85 V (3.41%)222.2 V12.94 V (5.63%)4315.7 WDrop High
300 mm²477 A372 A6.28 V (2.73%)223.7 V10.35 V (4.5%)3452.5 WDrop High
400 mm²570 A445 A4.71 V (2.05%)225.3 V7.77 V (3.38%)2589.4 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 80 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 550A at 80 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 80m at 230V (voltage drop: 4.71V or 2.05%).

What is the power capacity of 550A at 230V?

At unity power factor, 550A at 230V supports 126.5 kW with a standard 600A circuit breaker.