600 Amp Cable Size at 200 Meters (415V Three-Phase (UK / Australia Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 600 A over 200 m (656.2 ft).
Copper Cable (≤3% Drop)2× 400 mm²Drop: 5.56V (1.34%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 18.34V (4.42%)
Voltage at Load409.4 VLine Loss: 5778.0 W
Max Power & Breaker431.28 kW600A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 200m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 2965.27 V (714.52%) | 0.0 V | 4891.31 V (1178.63%) | 3081600.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1779.16 V (428.71%) | 0.0 V | 2934.79 V (707.18%) | 1848960.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 1111.98 V (267.95%) | 0.0 V | 1834.24 V (441.99%) | 1155600.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 741.32 V (178.63%) | 0.0 V | 1222.83 V (294.66%) | 770400.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 444.79 V (107.18%) | 0.0 V | 733.7 V (176.79%) | 462240.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 277.99 V (66.99%) | 137.0 V | 458.56 V (110.5%) | 288900.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 177.92 V (42.87%) | 237.1 V | 293.48 V (70.72%) | 184896.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 127.08 V (30.62%) | 287.9 V | 209.63 V (50.51%) | 132068.6 W | Drop High |
| 50 mm² | 151 A | 118 A | 88.96 V (21.44%) | 326.0 V | 146.74 V (35.36%) | 92448.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 63.54 V (15.31%) | 351.5 V | 104.81 V (25.26%) | 66034.3 W | Drop High |
| 95 mm² | 232 A | 181 A | 46.82 V (11.28%) | 368.2 V | 77.23 V (18.61%) | 48656.8 W | Drop High |
| 120 mm² | 269 A | 210 A | 37.07 V (8.93%) | 377.9 V | 61.14 V (14.73%) | 38520.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 29.65 V (7.15%) | 385.3 V | 48.91 V (11.79%) | 30816.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 24.04 V (5.79%) | 391.0 V | 39.66 V (9.56%) | 24985.9 W | Drop High |
| 240 mm² | 415 A | 324 A | 18.53 V (4.47%) | 396.5 V | 30.57 V (7.37%) | 19260.0 W | Drop High |
| 300 mm² | 477 A | 372 A | 14.83 V (3.57%) | 400.2 V | 24.46 V (5.89%) | 15408.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 11.12 V (2.68%) | 403.9 V | 18.34 V (4.42%) | 11556.0 W | Drop High |
FAQ — 600 Amp Cable Size at 200 Meters (415V Three-Phase (UK / Australia Industrial))
What mm² cable size is required for 600A at 200 meters (415V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 600A over 200m at 415V (voltage drop: 5.56V or 1.34%).
What is the power capacity of 600A at 415V?
At unity power factor, 600A at 415V supports 431.28 kW with a standard 600A circuit breaker.
Related Lengths & Currents (415V)
600A · 5m (415V)600A · 10m (415V)600A · 15m (415V)600A · 20m (415V)600A · 25m (415V)600A · 30m (415V)600A · 35m (415V)600A · 40m (415V)600A · 45m (415V)600A · 50m (415V)600A · 60m (415V)600A · 70m (415V)10A · 200m (415V)16A · 200m (415V)20A · 200m (415V)25A · 200m (415V)32A · 200m (415V)40A · 200m (415V)50A · 200m (415V)63A · 200m (415V)80A · 200m (415V)100A · 200m (415V)125A · 200m (415V)160A · 200m (415V)200A · 200m (415V)