600 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 600 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.95V (1.0%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 22.93V (3.32%)
Voltage at Load683.0 VLine Loss: 7222.5 W
Max Power & Breaker717.07 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3706.59 V (537.19%)0.0 V6114.14 V (886.11%)3852000.0 WDrop High
2.5 mm²24 A18 A2223.95 V (322.31%)0.0 V3668.48 V (531.66%)2311200.0 WDrop High
4 mm²32 A25 A1389.97 V (201.45%)0.0 V2292.8 V (332.29%)1444500.0 WDrop High
6 mm²41 A32 A926.65 V (134.3%)0.0 V1528.53 V (221.53%)963000.0 WDrop High
10 mm²57 A44 A555.99 V (80.58%)134.0 V917.12 V (132.92%)577800.0 WDrop High
16 mm²76 A59 A347.49 V (50.36%)342.5 V573.2 V (83.07%)361125.0 WDrop High
25 mm²101 A78 A222.4 V (32.23%)467.6 V366.85 V (53.17%)231120.0 WDrop High
35 mm²125 A97 A158.85 V (23.02%)531.1 V262.03 V (37.98%)165085.7 WDrop High
50 mm²151 A118 A111.2 V (16.12%)578.8 V183.42 V (26.58%)115560.0 WDrop High
70 mm²192 A150 A79.43 V (11.51%)610.6 V131.02 V (18.99%)82542.9 WDrop High
95 mm²232 A181 A58.53 V (8.48%)631.5 V96.54 V (13.99%)60821.1 WDrop High
120 mm²269 A210 A46.33 V (6.71%)643.7 V76.43 V (11.08%)48150.0 WDrop High
150 mm²309 A241 A37.07 V (5.37%)652.9 V61.14 V (8.86%)38520.0 WDrop High
185 mm²353 A275 A30.05 V (4.36%)659.9 V49.57 V (7.18%)31232.4 WDrop High
240 mm²415 A324 A23.17 V (3.36%)666.8 V38.21 V (5.54%)24075.0 WDrop High
300 mm²477 A372 A18.53 V (2.69%)671.5 V30.57 V (4.43%)19260.0 WDrop High
400 mm²570 A445 A13.9 V (2.01%)676.1 V22.93 V (3.32%)14445.0 WDrop High

FAQ — 600 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 600A at 250 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 600A over 250m at 690V (voltage drop: 6.95V or 1.0%).

What is the power capacity of 600A at 690V?

At unity power factor, 600A at 690V supports 717.07 kW with a standard 600A circuit breaker.