600 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 600 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 8.34V (1.21%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 27.51V (3.99%)
Voltage at Load681.7 VLine Loss: 8667.0 W
Max Power & Breaker717.07 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4447.91 V (644.62%)0.0 V7336.97 V (1063.33%)4622400.0 WDrop High
2.5 mm²24 A18 A2668.74 V (386.77%)0.0 V4402.18 V (638.0%)2773440.0 WDrop High
4 mm²32 A25 A1667.96 V (241.73%)0.0 V2751.36 V (398.75%)1733400.0 WDrop High
6 mm²41 A32 A1111.98 V (161.16%)0.0 V1834.24 V (265.83%)1155600.0 WDrop High
10 mm²57 A44 A667.19 V (96.69%)22.8 V1100.55 V (159.5%)693360.0 WDrop High
16 mm²76 A59 A416.99 V (60.43%)273.0 V687.84 V (99.69%)433350.0 WDrop High
25 mm²101 A78 A266.87 V (38.68%)423.1 V440.22 V (63.8%)277344.0 WDrop High
35 mm²125 A97 A190.62 V (27.63%)499.4 V314.44 V (45.57%)198102.9 WDrop High
50 mm²151 A118 A133.44 V (19.34%)556.6 V220.11 V (31.9%)138672.0 WDrop High
70 mm²192 A150 A95.31 V (13.81%)594.7 V157.22 V (22.79%)99051.4 WDrop High
95 mm²232 A181 A70.23 V (10.18%)619.8 V115.85 V (16.79%)72985.3 WDrop High
120 mm²269 A210 A55.6 V (8.06%)634.4 V91.71 V (13.29%)57780.0 WDrop High
150 mm²309 A241 A44.48 V (6.45%)645.5 V73.37 V (10.63%)46224.0 WDrop High
185 mm²353 A275 A36.06 V (5.23%)653.9 V59.49 V (8.62%)37478.9 WDrop High
240 mm²415 A324 A27.8 V (4.03%)662.2 V45.86 V (6.65%)28890.0 WDrop High
300 mm²477 A372 A22.24 V (3.22%)667.8 V36.68 V (5.32%)23112.0 WDrop High
400 mm²570 A445 A16.68 V (2.42%)673.3 V27.51 V (3.99%)17334.0 WDrop High

FAQ — 600 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 600A at 300 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 600A over 300m at 690V (voltage drop: 8.34V or 1.21%).

What is the power capacity of 600A at 690V?

At unity power factor, 600A at 690V supports 717.07 kW with a standard 600A circuit breaker.