600 Amp Cable Size at 350 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 600 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)4× 400 mm²Drop: 5.62V (2.44%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 37.06V (16.12%)
Voltage at Load224.4 VLine Loss: 3370.5 W
Max Power & Breaker138.0 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5992.0 V (2605.22%)0.0 V9884.0 V (4297.39%)3595200.0 WDrop High
2.5 mm²24 A18 A3595.2 V (1563.13%)0.0 V5930.4 V (2578.43%)2157120.0 WDrop High
4 mm²32 A25 A2247.0 V (976.96%)0.0 V3706.5 V (1611.52%)1348200.0 WDrop High
6 mm²41 A32 A1498.0 V (651.3%)0.0 V2471.0 V (1074.35%)898800.0 WDrop High
10 mm²57 A44 A898.8 V (390.78%)0.0 V1482.6 V (644.61%)539280.0 WDrop High
16 mm²76 A59 A561.75 V (244.24%)0.0 V926.62 V (402.88%)337050.0 WDrop High
25 mm²101 A78 A359.52 V (156.31%)0.0 V593.04 V (257.84%)215712.0 WDrop High
35 mm²125 A97 A256.8 V (111.65%)0.0 V423.6 V (184.17%)154080.0 WDrop High
50 mm²151 A118 A179.76 V (78.16%)50.2 V296.52 V (128.92%)107856.0 WDrop High
70 mm²192 A150 A128.4 V (55.83%)101.6 V211.8 V (92.09%)77040.0 WDrop High
95 mm²232 A181 A94.61 V (41.14%)135.4 V156.06 V (67.85%)56766.3 WDrop High
120 mm²269 A210 A74.9 V (32.57%)155.1 V123.55 V (53.72%)44940.0 WDrop High
150 mm²309 A241 A59.92 V (26.05%)170.1 V98.84 V (42.97%)35952.0 WDrop High
185 mm²353 A275 A48.58 V (21.12%)181.4 V80.14 V (34.84%)29150.3 WDrop High
240 mm²415 A324 A37.45 V (16.28%)192.6 V61.77 V (26.86%)22470.0 WDrop High
300 mm²477 A372 A29.96 V (13.03%)200.0 V49.42 V (21.49%)17976.0 WDrop High
400 mm²570 A445 A22.47 V (9.77%)207.5 V37.06 V (16.12%)13482.0 WDrop High

FAQ — 600 Amp Cable Size at 350 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 600A at 350 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4× 400 mm² copper cable for 600A over 350m at 230V (voltage drop: 5.62V or 2.44%).

What is the power capacity of 600A at 230V?

At unity power factor, 600A at 230V supports 138.0 kW with a standard 600A circuit breaker.