600 Amp Cable Size at 45 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 600 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.45V (0.63%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.77V (2.07%)
Voltage at Load228.6 VLine Loss: 866.7 W
Max Power & Breaker138.0 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A770.4 V (334.96%)0.0 V1270.8 V (552.52%)462240.0 WDrop High
2.5 mm²24 A18 A462.24 V (200.97%)0.0 V762.48 V (331.51%)277344.0 WDrop High
4 mm²32 A25 A288.9 V (125.61%)0.0 V476.55 V (207.2%)173340.0 WDrop High
6 mm²41 A32 A192.6 V (83.74%)37.4 V317.7 V (138.13%)115560.0 WDrop High
10 mm²57 A44 A115.56 V (50.24%)114.4 V190.62 V (82.88%)69336.0 WDrop High
16 mm²76 A59 A72.22 V (31.4%)157.8 V119.14 V (51.8%)43335.0 WDrop High
25 mm²101 A78 A46.22 V (20.1%)183.8 V76.25 V (33.15%)27734.4 WDrop High
35 mm²125 A97 A33.02 V (14.36%)197.0 V54.46 V (23.68%)19810.3 WDrop High
50 mm²151 A118 A23.11 V (10.05%)206.9 V38.12 V (16.58%)13867.2 WDrop High
70 mm²192 A150 A16.51 V (7.18%)213.5 V27.23 V (11.84%)9905.1 WDrop High
95 mm²232 A181 A12.16 V (5.29%)217.8 V20.07 V (8.72%)7298.5 WDrop High
120 mm²269 A210 A9.63 V (4.19%)220.4 V15.88 V (6.91%)5778.0 WDrop High
150 mm²309 A241 A7.7 V (3.35%)222.3 V12.71 V (5.53%)4622.4 WDrop High
185 mm²353 A275 A6.25 V (2.72%)223.8 V10.3 V (4.48%)3747.9 WDrop High
240 mm²415 A324 A4.81 V (2.09%)225.2 V7.94 V (3.45%)2889.0 WDrop High
300 mm²477 A372 A3.85 V (1.67%)226.1 V6.35 V (2.76%)2311.2 WDrop High
400 mm²570 A445 A2.89 V (1.26%)227.1 V4.77 V (2.07%)1733.4 WDrop High

FAQ — 600 Amp Cable Size at 45 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 600A at 45 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 600A over 45m at 230V (voltage drop: 1.45V or 0.63%).

What is the power capacity of 600A at 230V?

At unity power factor, 600A at 230V supports 138.0 kW with a standard 600A circuit breaker.