600 Amp Cable Size at 500 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 600 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 9.27V (2.23%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 45.86V (11.05%)
Voltage at Load405.7 VLine Loss: 9630.0 W
Max Power & Breaker431.28 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7413.18 V (1786.31%)0.0 V12228.28 V (2946.57%)7704000.0 WDrop High
2.5 mm²24 A18 A4447.91 V (1071.78%)0.0 V7336.97 V (1767.94%)4622400.0 WDrop High
4 mm²32 A25 A2779.94 V (669.87%)0.0 V4585.6 V (1104.96%)2889000.0 WDrop High
6 mm²41 A32 A1853.29 V (446.58%)0.0 V3057.07 V (736.64%)1926000.0 WDrop High
10 mm²57 A44 A1111.98 V (267.95%)0.0 V1834.24 V (441.99%)1155600.0 WDrop High
16 mm²76 A59 A694.99 V (167.47%)0.0 V1146.4 V (276.24%)722250.0 WDrop High
25 mm²101 A78 A444.79 V (107.18%)0.0 V733.7 V (176.79%)462240.0 WDrop High
35 mm²125 A97 A317.71 V (76.56%)97.3 V524.07 V (126.28%)330171.4 WDrop High
50 mm²151 A118 A222.4 V (53.59%)192.6 V366.85 V (88.4%)231120.0 WDrop High
70 mm²192 A150 A158.85 V (38.28%)256.1 V262.03 V (63.14%)165085.7 WDrop High
95 mm²232 A181 A117.05 V (28.2%)297.9 V193.08 V (46.52%)121642.1 WDrop High
120 mm²269 A210 A92.66 V (22.33%)322.3 V152.85 V (36.83%)96300.0 WDrop High
150 mm²309 A241 A74.13 V (17.86%)340.9 V122.28 V (29.47%)77040.0 WDrop High
185 mm²353 A275 A60.11 V (14.48%)354.9 V99.15 V (23.89%)62464.9 WDrop High
240 mm²415 A324 A46.33 V (11.16%)368.7 V76.43 V (18.42%)48150.0 WDrop High
300 mm²477 A372 A37.07 V (8.93%)377.9 V61.14 V (14.73%)38520.0 WDrop High
400 mm²570 A445 A27.8 V (6.7%)387.2 V45.86 V (11.05%)28890.0 WDrop High

FAQ — 600 Amp Cable Size at 500 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 600A at 500 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 600A over 500m at 415V (voltage drop: 9.27V or 2.23%).

What is the power capacity of 600A at 415V?

At unity power factor, 600A at 415V supports 431.28 kW with a standard 600A circuit breaker.