63 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 63 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 1.44V (3.0%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 1.19V (2.47%)
Voltage at Load46.6 VLine Loss: 90.6 W
Max Power & Breaker3.02 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A143.81 V (299.6%)0.0 V237.22 V (494.2%)9059.9 WDrop High
2.5 mm²24 A18 A86.28 V (179.76%)0.0 V142.33 V (296.52%)5435.9 WDrop High
4 mm²32 A25 A53.93 V (112.35%)0.0 V88.96 V (185.32%)3397.5 WDrop High
6 mm²41 A32 A35.95 V (74.9%)12.0 V59.3 V (123.55%)2265.0 WDrop High
10 mm²57 A44 A21.57 V (44.94%)26.4 V35.58 V (74.13%)1359.0 WDrop High
16 mm²76 A59 A13.48 V (28.09%)34.5 V22.24 V (46.33%)849.4 WDrop High
25 mm²101 A78 A8.63 V (17.98%)39.4 V14.23 V (29.65%)543.6 WDrop High
35 mm²125 A97 A6.16 V (12.84%)41.8 V10.17 V (21.18%)388.3 WDrop High
50 mm²151 A118 A4.31 V (8.99%)43.7 V7.12 V (14.83%)271.8 WDrop High
70 mm²192 A150 A3.08 V (6.42%)44.9 V5.08 V (10.59%)194.1 WDrop High
95 mm²232 A181 A2.27 V (4.73%)45.7 V3.75 V (7.8%)143.1 W~ ≤5%
120 mm²269 A210 A1.8 V (3.75%)46.2 V2.97 V (6.18%)113.2 W~ ≤5%
150 mm²309 A241 A1.44 V (3.0%)46.6 V2.37 V (4.94%)90.6 W✓ OK (≤3%)
185 mm²353 A275 A1.17 V (2.43%)46.8 V1.92 V (4.01%)73.5 W✓ OK (≤3%)
240 mm²415 A324 A0.9 V (1.87%)47.1 V1.48 V (3.09%)56.6 W✓ OK (≤3%)
300 mm²477 A372 A0.72 V (1.5%)47.3 V1.19 V (2.47%)45.3 W✓ OK (≤3%)
400 mm²570 A445 A0.54 V (1.12%)47.5 V0.89 V (1.85%)34.0 W✓ OK (≤3%)

FAQ — 63 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 63A at 80 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 63A over 80m at 48V (voltage drop: 1.44V or 3.0%).

What is the power capacity of 63A at 48V?

At unity power factor, 63A at 48V supports 3.02 kW with a standard 63A circuit breaker.