⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

16 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 1.1V (2.28%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 1.29V (2.69%)
Voltage at Load46.9 VLine Loss: 17.5 W
Max Power & Breaker0.77 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A36.52 V (76.09%)11.5 V60.25 V (125.51%)584.4 WDrop High
2.5 mm²24 A18 A21.91 V (45.65%)26.1 V36.15 V (75.31%)350.6 WDrop High
4 mm²32 A25 A13.7 V (28.53%)34.3 V22.59 V (47.07%)219.1 WDrop High
6 mm²41 A32 A9.13 V (19.02%)38.9 V15.06 V (31.38%)146.1 WDrop High
10 mm²57 A44 A5.48 V (11.41%)42.5 V9.04 V (18.83%)87.7 WDrop High
16 mm²76 A59 A3.42 V (7.13%)44.6 V5.65 V (11.77%)54.8 WDrop High
25 mm²101 A78 A2.19 V (4.57%)45.8 V3.61 V (7.53%)35.1 W~ ≤5%
35 mm²125 A97 A1.57 V (3.26%)46.4 V2.58 V (5.38%)25.0 W~ ≤5%
50 mm²151 A118 A1.1 V (2.28%)46.9 V1.81 V (3.77%)17.5 W✓ OK (≤3%)
70 mm²192 A150 A0.78 V (1.63%)47.2 V1.29 V (2.69%)12.5 W✓ OK (≤3%)
95 mm²232 A181 A0.58 V (1.2%)47.4 V0.95 V (1.98%)9.2 W✓ OK (≤3%)
120 mm²269 A210 A0.46 V (0.95%)47.5 V0.75 V (1.57%)7.3 W✓ OK (≤3%)
150 mm²309 A241 A0.37 V (0.76%)47.6 V0.6 V (1.26%)5.8 W✓ OK (≤3%)
185 mm²353 A275 A0.3 V (0.62%)47.7 V0.49 V (1.02%)4.7 W✓ OK (≤3%)
240 mm²415 A324 A0.23 V (0.48%)47.8 V0.38 V (0.78%)3.7 W✓ OK (≤3%)
300 mm²477 A372 A0.18 V (0.38%)47.8 V0.3 V (0.63%)2.9 W✓ OK (≤3%)
400 mm²570 A445 A0.14 V (0.29%)47.9 V0.23 V (0.47%)2.2 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 16A at 80 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 16A over 80m at 48V (voltage drop: 1.1V or 2.28%).

What is the power capacity of 16A at 48V?

At unity power factor, 16A at 48V supports 0.77 kW with a standard 16A circuit breaker.