100 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 100 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 1.43V (2.97%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.41V (2.94%)
Voltage at Load46.6 VLine Loss: 142.7 W
Max Power & Breaker4.8 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A228.27 V (475.56%)0.0 V376.53 V (784.44%)22826.7 WDrop High
2.5 mm²24 A18 A136.96 V (285.33%)0.0 V225.92 V (470.67%)13696.0 WDrop High
4 mm²32 A25 A85.6 V (178.33%)0.0 V141.2 V (294.17%)8560.0 WDrop High
6 mm²41 A32 A57.07 V (118.89%)0.0 V94.13 V (196.11%)5706.7 WDrop High
10 mm²57 A44 A34.24 V (71.33%)13.8 V56.48 V (117.67%)3424.0 WDrop High
16 mm²76 A59 A21.4 V (44.58%)26.6 V35.3 V (73.54%)2140.0 WDrop High
25 mm²101 A78 A13.7 V (28.53%)34.3 V22.59 V (47.07%)1369.6 WDrop High
35 mm²125 A97 A9.78 V (20.38%)38.2 V16.14 V (33.62%)978.3 WDrop High
50 mm²151 A118 A6.85 V (14.27%)41.2 V11.3 V (23.53%)684.8 WDrop High
70 mm²192 A150 A4.89 V (10.19%)43.1 V8.07 V (16.81%)489.1 WDrop High
95 mm²232 A181 A3.6 V (7.51%)44.4 V5.95 V (12.39%)360.4 WDrop High
120 mm²269 A210 A2.85 V (5.94%)45.1 V4.71 V (9.81%)285.3 WDrop High
150 mm²309 A241 A2.28 V (4.76%)45.7 V3.77 V (7.84%)228.3 W~ ≤5%
185 mm²353 A275 A1.85 V (3.86%)46.1 V3.05 V (6.36%)185.1 W~ ≤5%
240 mm²415 A324 A1.43 V (2.97%)46.6 V2.35 V (4.9%)142.7 W✓ OK (≤3%)
300 mm²477 A372 A1.14 V (2.38%)46.9 V1.88 V (3.92%)114.1 W✓ OK (≤3%)
400 mm²570 A445 A0.86 V (1.78%)47.1 V1.41 V (2.94%)85.6 W✓ OK (≤3%)

FAQ — 100 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 100A at 80 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 100A over 80m at 48V (voltage drop: 1.43V or 2.97%).

What is the power capacity of 100A at 48V?

At unity power factor, 100A at 48V supports 4.8 kW with a standard 100A circuit breaker.