700 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)10× 400 mm²Drop: 1.31V (2.73%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 21.62V (45.04%)
Voltage at Load46.7 VLine Loss: 917.5 W
Max Power & Breaker33.6 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3495.33 V (7281.94%)0.0 V5765.67 V (12011.81%)2446733.3 WDrop High
2.5 mm²24 A18 A2097.2 V (4369.17%)0.0 V3459.4 V (7207.08%)1468040.0 WDrop High
4 mm²32 A25 A1310.75 V (2730.73%)0.0 V2162.12 V (4504.43%)917525.0 WDrop High
6 mm²41 A32 A873.83 V (1820.49%)0.0 V1441.42 V (3002.95%)611683.3 WDrop High
10 mm²57 A44 A524.3 V (1092.29%)0.0 V864.85 V (1801.77%)367010.0 WDrop High
16 mm²76 A59 A327.69 V (682.68%)0.0 V540.53 V (1126.11%)229381.2 WDrop High
25 mm²101 A78 A209.72 V (436.92%)0.0 V345.94 V (720.71%)146804.0 WDrop High
35 mm²125 A97 A149.8 V (312.08%)0.0 V247.1 V (514.79%)104860.0 WDrop High
50 mm²151 A118 A104.86 V (218.46%)0.0 V172.97 V (360.35%)73402.0 WDrop High
70 mm²192 A150 A74.9 V (156.04%)0.0 V123.55 V (257.4%)52430.0 WDrop High
95 mm²232 A181 A55.19 V (114.98%)0.0 V91.04 V (189.66%)38632.6 WDrop High
120 mm²269 A210 A43.69 V (91.02%)4.3 V72.07 V (150.15%)30584.2 WDrop High
150 mm²309 A241 A34.95 V (72.82%)13.0 V57.66 V (120.12%)24467.3 WDrop High
185 mm²353 A275 A28.34 V (59.04%)19.7 V46.75 V (97.39%)19838.4 WDrop High
240 mm²415 A324 A21.85 V (45.51%)26.2 V36.04 V (75.07%)15292.1 WDrop High
300 mm²477 A372 A17.48 V (36.41%)30.5 V28.83 V (60.06%)12233.7 WDrop High
400 mm²570 A445 A13.11 V (27.31%)34.9 V21.62 V (45.04%)9175.2 WDrop High

FAQ — 700 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 700A at 175 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10× 400 mm² copper cable for 700A over 175m at 48V (voltage drop: 1.31V or 2.73%).

What is the power capacity of 700A at 48V?

At unity power factor, 700A at 48V supports 33.6 kW with a standard 700A circuit breaker.