700 Amp Cable Size at 500 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)6× 400 mm²Drop: 6.24V (2.71%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 61.77V (26.86%)
Voltage at Load223.8 VLine Loss: 4369.2 W
Max Power & Breaker161.0 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A9986.67 V (4342.03%)0.0 V16473.33 V (7162.32%)6990666.7 WDrop High
2.5 mm²24 A18 A5992.0 V (2605.22%)0.0 V9884.0 V (4297.39%)4194400.0 WDrop High
4 mm²32 A25 A3745.0 V (1628.26%)0.0 V6177.5 V (2685.87%)2621500.0 WDrop High
6 mm²41 A32 A2496.67 V (1085.51%)0.0 V4118.33 V (1790.58%)1747666.7 WDrop High
10 mm²57 A44 A1498.0 V (651.3%)0.0 V2471.0 V (1074.35%)1048600.0 WDrop High
16 mm²76 A59 A936.25 V (407.07%)0.0 V1544.37 V (671.47%)655375.0 WDrop High
25 mm²101 A78 A599.2 V (260.52%)0.0 V988.4 V (429.74%)419440.0 WDrop High
35 mm²125 A97 A428.0 V (186.09%)0.0 V706.0 V (306.96%)299600.0 WDrop High
50 mm²151 A118 A299.6 V (130.26%)0.0 V494.2 V (214.87%)209720.0 WDrop High
70 mm²192 A150 A214.0 V (93.04%)16.0 V353.0 V (153.48%)149800.0 WDrop High
95 mm²232 A181 A157.68 V (68.56%)72.3 V260.11 V (113.09%)110378.9 WDrop High
120 mm²269 A210 A124.83 V (54.28%)105.2 V205.92 V (89.53%)87383.3 WDrop High
150 mm²309 A241 A99.87 V (43.42%)130.1 V164.73 V (71.62%)69906.7 WDrop High
185 mm²353 A275 A80.97 V (35.21%)149.0 V133.57 V (58.07%)56681.1 WDrop High
240 mm²415 A324 A62.42 V (27.14%)167.6 V102.96 V (44.76%)43691.7 WDrop High
300 mm²477 A372 A49.93 V (21.71%)180.1 V82.37 V (35.81%)34953.3 WDrop High
400 mm²570 A445 A37.45 V (16.28%)192.6 V61.77 V (26.86%)26215.0 WDrop High

FAQ — 700 Amp Cable Size at 500 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 700A at 500 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6× 400 mm² copper cable for 700A over 500m at 230V (voltage drop: 6.24V or 2.71%).

What is the power capacity of 700A at 230V?

At unity power factor, 700A at 230V supports 161.0 kW with a standard 700A circuit breaker.