⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

700 Amp Cable Size at 5 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.18V (0.08%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.62V (0.27%)
Voltage at Load229.8 VLine Loss: 131.1 W
Max Power & Breaker161.0 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A99.87 V (43.42%)130.1 V164.73 V (71.62%)69906.7 WDrop High
2.5 mm²24 A18 A59.92 V (26.05%)170.1 V98.84 V (42.97%)41944.0 WDrop High
4 mm²32 A25 A37.45 V (16.28%)192.6 V61.77 V (26.86%)26215.0 WDrop High
6 mm²41 A32 A24.97 V (10.86%)205.0 V41.18 V (17.91%)17476.7 WDrop High
10 mm²57 A44 A14.98 V (6.51%)215.0 V24.71 V (10.74%)10486.0 WDrop High
16 mm²76 A59 A9.36 V (4.07%)220.6 V15.44 V (6.71%)6553.8 WDrop High
25 mm²101 A78 A5.99 V (2.61%)224.0 V9.88 V (4.3%)4194.4 WDrop High
35 mm²125 A97 A4.28 V (1.86%)225.7 V7.06 V (3.07%)2996.0 WDrop High
50 mm²151 A118 A3.0 V (1.3%)227.0 V4.94 V (2.15%)2097.2 WDrop High
70 mm²192 A150 A2.14 V (0.93%)227.9 V3.53 V (1.53%)1498.0 WDrop High
95 mm²232 A181 A1.58 V (0.69%)228.4 V2.6 V (1.13%)1103.8 WDrop High
120 mm²269 A210 A1.25 V (0.54%)228.8 V2.06 V (0.9%)873.8 WDrop High
150 mm²309 A241 A1.0 V (0.43%)229.0 V1.65 V (0.72%)699.1 WDrop High
185 mm²353 A275 A0.81 V (0.35%)229.2 V1.34 V (0.58%)566.8 WDrop High
240 mm²415 A324 A0.62 V (0.27%)229.4 V1.03 V (0.45%)436.9 WDrop High
300 mm²477 A372 A0.5 V (0.22%)229.5 V0.82 V (0.36%)349.5 WDrop High
400 mm²570 A445 A0.37 V (0.16%)229.6 V0.62 V (0.27%)262.1 WDrop High

FAQ — 700 Amp Cable Size at 5 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 700A at 5 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 5m at 230V (voltage drop: 0.18V or 0.08%).

What is the power capacity of 700A at 230V?

At unity power factor, 700A at 230V supports 161.0 kW with a standard 700A circuit breaker.