750 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 750 A over 175 m (574.1 ft).
Copper Cable (≤3% Drop)10× 400 mm²Drop: 1.4V (2.93%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 23.17V (48.26%)
Voltage at Load46.6 VLine Loss: 1053.3 W
Max Power & Breaker36.0 kW800A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 175m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 3745.0 V (7802.08%) | 0.0 V | 6177.5 V (12869.79%) | 2808750.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 2247.0 V (4681.25%) | 0.0 V | 3706.5 V (7721.87%) | 1685250.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 1404.37 V (2925.78%) | 0.0 V | 2316.56 V (4826.17%) | 1053281.2 W | Drop High |
| 6 mm² | 41 A | 32 A | 936.25 V (1950.52%) | 0.0 V | 1544.38 V (3217.45%) | 702187.5 W | Drop High |
| 10 mm² | 57 A | 44 A | 561.75 V (1170.31%) | 0.0 V | 926.62 V (1930.47%) | 421312.5 W | Drop High |
| 16 mm² | 76 A | 59 A | 351.09 V (731.45%) | 0.0 V | 579.14 V (1206.54%) | 263320.3 W | Drop High |
| 25 mm² | 101 A | 78 A | 224.7 V (468.12%) | 0.0 V | 370.65 V (772.19%) | 168525.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 160.5 V (334.37%) | 0.0 V | 264.75 V (551.56%) | 120375.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 112.35 V (234.06%) | 0.0 V | 185.32 V (386.09%) | 84262.5 W | Drop High |
| 70 mm² | 192 A | 150 A | 80.25 V (167.19%) | 0.0 V | 132.38 V (275.78%) | 60187.5 W | Drop High |
| 95 mm² | 232 A | 181 A | 59.13 V (123.19%) | 0.0 V | 97.54 V (203.21%) | 44348.7 W | Drop High |
| 120 mm² | 269 A | 210 A | 46.81 V (97.53%) | 1.2 V | 77.22 V (160.87%) | 35109.4 W | Drop High |
| 150 mm² | 309 A | 241 A | 37.45 V (78.02%) | 10.6 V | 61.77 V (128.7%) | 28087.5 W | Drop High |
| 185 mm² | 353 A | 275 A | 30.36 V (63.26%) | 17.6 V | 50.09 V (104.35%) | 22773.6 W | Drop High |
| 240 mm² | 415 A | 324 A | 23.41 V (48.76%) | 24.6 V | 38.61 V (80.44%) | 17554.7 W | Drop High |
| 300 mm² | 477 A | 372 A | 18.72 V (39.01%) | 29.3 V | 30.89 V (64.35%) | 14043.7 W | Drop High |
| 400 mm² | 570 A | 445 A | 14.04 V (29.26%) | 34.0 V | 23.17 V (48.26%) | 10532.8 W | Drop High |
FAQ — 750 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))
What mm² cable size is required for 750A at 175 meters (48V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10× 400 mm² copper cable for 750A over 175m at 48V (voltage drop: 1.4V or 2.93%).
What is the power capacity of 750A at 48V?
At unity power factor, 750A at 48V supports 36.0 kW with a standard 800A circuit breaker.
Related Lengths & Currents (48V)
750A · 5m (48V)750A · 10m (48V)750A · 15m (48V)750A · 20m (48V)750A · 25m (48V)750A · 30m (48V)750A · 35m (48V)750A · 40m (48V)750A · 45m (48V)750A · 50m (48V)750A · 60m (48V)750A · 70m (48V)10A · 175m (48V)16A · 175m (48V)20A · 175m (48V)25A · 175m (48V)32A · 175m (48V)40A · 175m (48V)50A · 175m (48V)63A · 175m (48V)80A · 175m (48V)100A · 175m (48V)125A · 175m (48V)160A · 175m (48V)200A · 175m (48V)