750 Amp Cable Size at 35 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 750 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.41V (2.92%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.63V (9.65%)
Voltage at Load46.6 VLine Loss: 1053.3 W
Max Power & Breaker36.0 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A749.0 V (1560.42%)0.0 V1235.5 V (2573.96%)561750.0 WDrop High
2.5 mm²24 A18 A449.4 V (936.25%)0.0 V741.3 V (1544.38%)337050.0 WDrop High
4 mm²32 A25 A280.88 V (585.16%)0.0 V463.31 V (965.23%)210656.2 WDrop High
6 mm²41 A32 A187.25 V (390.1%)0.0 V308.88 V (643.49%)140437.5 WDrop High
10 mm²57 A44 A112.35 V (234.06%)0.0 V185.33 V (386.09%)84262.5 WDrop High
16 mm²76 A59 A70.22 V (146.29%)0.0 V115.83 V (241.31%)52664.1 WDrop High
25 mm²101 A78 A44.94 V (93.62%)3.1 V74.13 V (154.44%)33705.0 WDrop High
35 mm²125 A97 A32.1 V (66.88%)15.9 V52.95 V (110.31%)24075.0 WDrop High
50 mm²151 A118 A22.47 V (46.81%)25.5 V37.06 V (77.22%)16852.5 WDrop High
70 mm²192 A150 A16.05 V (33.44%)31.9 V26.47 V (55.16%)12037.5 WDrop High
95 mm²232 A181 A11.83 V (24.64%)36.2 V19.51 V (40.64%)8869.7 WDrop High
120 mm²269 A210 A9.36 V (19.51%)38.6 V15.44 V (32.17%)7021.9 WDrop High
150 mm²309 A241 A7.49 V (15.6%)40.5 V12.36 V (25.74%)5617.5 WDrop High
185 mm²353 A275 A6.07 V (12.65%)41.9 V10.02 V (20.87%)4554.7 WDrop High
240 mm²415 A324 A4.68 V (9.75%)43.3 V7.72 V (16.09%)3510.9 WDrop High
300 mm²477 A372 A3.74 V (7.8%)44.3 V6.18 V (12.87%)2808.8 WDrop High
400 mm²570 A445 A2.81 V (5.85%)45.2 V4.63 V (9.65%)2106.6 WDrop High

FAQ — 750 Amp Cable Size at 35 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 750A at 35 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 750A over 35m at 48V (voltage drop: 1.41V or 2.92%).

What is the power capacity of 750A at 48V?

At unity power factor, 750A at 48V supports 36.0 kW with a standard 800A circuit breaker.