⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

750 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 750 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.17V (0.04%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.57V (0.14%)
Voltage at Load414.8 VLine Loss: 225.7 W
Max Power & Breaker539.1 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A92.66 V (22.33%)322.3 V152.85 V (36.83%)120375.0 WDrop High
2.5 mm²24 A18 A55.6 V (13.4%)359.4 V91.71 V (22.1%)72225.0 WDrop High
4 mm²32 A25 A34.75 V (8.37%)380.3 V57.32 V (13.81%)45140.6 WDrop High
6 mm²41 A32 A23.17 V (5.58%)391.8 V38.21 V (9.21%)30093.8 WDrop High
10 mm²57 A44 A13.9 V (3.35%)401.1 V22.93 V (5.52%)18056.2 WDrop High
16 mm²76 A59 A8.69 V (2.09%)406.3 V14.33 V (3.45%)11285.2 WDrop High
25 mm²101 A78 A5.56 V (1.34%)409.4 V9.17 V (2.21%)7222.5 WDrop High
35 mm²125 A97 A3.97 V (0.96%)411.0 V6.55 V (1.58%)5158.9 WDrop High
50 mm²151 A118 A2.78 V (0.67%)412.2 V4.59 V (1.1%)3611.2 WDrop High
70 mm²192 A150 A1.99 V (0.48%)413.0 V3.28 V (0.79%)2579.5 WDrop High
95 mm²232 A181 A1.46 V (0.35%)413.5 V2.41 V (0.58%)1900.7 WDrop High
120 mm²269 A210 A1.16 V (0.28%)413.8 V1.91 V (0.46%)1504.7 WDrop High
150 mm²309 A241 A0.93 V (0.22%)414.1 V1.53 V (0.37%)1203.8 WDrop High
185 mm²353 A275 A0.75 V (0.18%)414.2 V1.24 V (0.3%)976.0 WDrop High
240 mm²415 A324 A0.58 V (0.14%)414.4 V0.96 V (0.23%)752.3 WDrop High
300 mm²477 A372 A0.46 V (0.11%)414.5 V0.76 V (0.18%)601.9 WDrop High
400 mm²570 A445 A0.35 V (0.08%)414.7 V0.57 V (0.14%)451.4 WDrop High

FAQ — 750 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 750A at 5 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 750A over 5m at 415V (voltage drop: 0.17V or 0.04%).

What is the power capacity of 750A at 415V?

At unity power factor, 750A at 415V supports 539.1 kW with a standard 800A circuit breaker.