⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

25 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 1.16V (0.28%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 1.91V (0.46%)
Voltage at Load413.8 VLine Loss: 50.2 W
Max Power & Breaker17.97 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3.09 V (0.74%)411.9 V5.1 V (1.23%)133.8 WDrop High
2.5 mm²24 A18 A1.85 V (0.45%)413.1 V3.06 V (0.74%)80.2 WDrop High
4 mm²32 A25 A1.16 V (0.28%)413.8 V1.91 V (0.46%)50.2 W✓ OK (≤3%)
6 mm²41 A32 A0.77 V (0.19%)414.2 V1.27 V (0.31%)33.4 W✓ OK (≤3%)
10 mm²57 A44 A0.46 V (0.11%)414.5 V0.76 V (0.18%)20.1 W✓ OK (≤3%)
16 mm²76 A59 A0.29 V (0.07%)414.7 V0.48 V (0.12%)12.5 W✓ OK (≤3%)
25 mm²101 A78 A0.19 V (0.04%)414.8 V0.31 V (0.07%)8.0 W✓ OK (≤3%)
35 mm²125 A97 A0.13 V (0.03%)414.9 V0.22 V (0.05%)5.7 W✓ OK (≤3%)
50 mm²151 A118 A0.09 V (0.02%)414.9 V0.15 V (0.04%)4.0 W✓ OK (≤3%)
70 mm²192 A150 A0.07 V (0.02%)414.9 V0.11 V (0.03%)2.9 W✓ OK (≤3%)
95 mm²232 A181 A0.05 V (0.01%)415.0 V0.08 V (0.02%)2.1 W✓ OK (≤3%)
120 mm²269 A210 A0.04 V (0.01%)415.0 V0.06 V (0.02%)1.7 W✓ OK (≤3%)
150 mm²309 A241 A0.03 V (0.01%)415.0 V0.05 V (0.01%)1.3 W✓ OK (≤3%)
185 mm²353 A275 A0.03 V (0.01%)415.0 V0.04 V (0.01%)1.1 W✓ OK (≤3%)
240 mm²415 A324 A0.02 V (0.0%)415.0 V0.03 V (0.01%)0.8 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.0%)415.0 V0.03 V (0.01%)0.7 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.0%)415.0 V0.02 V (0.0%)0.5 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 25A at 5 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 25A over 5m at 415V (voltage drop: 1.16V or 0.28%).

What is the power capacity of 25A at 415V?

At unity power factor, 25A at 415V supports 17.97 kW with a standard 25A circuit breaker.