750 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 750 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.87V (0.21%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.87V (0.69%)
Voltage at Load414.1 VLine Loss: 1128.5 W
Max Power & Breaker539.1 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A463.32 V (111.64%)0.0 V764.27 V (184.16%)601875.0 WDrop High
2.5 mm²24 A18 A277.99 V (66.99%)137.0 V458.56 V (110.5%)361125.0 WDrop High
4 mm²32 A25 A173.75 V (41.87%)241.3 V286.6 V (69.06%)225703.1 WDrop High
6 mm²41 A32 A115.83 V (27.91%)299.2 V191.07 V (46.04%)150468.7 WDrop High
10 mm²57 A44 A69.5 V (16.75%)345.5 V114.64 V (27.62%)90281.2 WDrop High
16 mm²76 A59 A43.44 V (10.47%)371.6 V71.65 V (17.27%)56425.8 WDrop High
25 mm²101 A78 A27.8 V (6.7%)387.2 V45.86 V (11.05%)36112.5 WDrop High
35 mm²125 A97 A19.86 V (4.78%)395.1 V32.75 V (7.89%)25794.6 WDrop High
50 mm²151 A118 A13.9 V (3.35%)401.1 V22.93 V (5.52%)18056.2 WDrop High
70 mm²192 A150 A9.93 V (2.39%)405.1 V16.38 V (3.95%)12897.3 WDrop High
95 mm²232 A181 A7.32 V (1.76%)407.7 V12.07 V (2.91%)9503.3 WDrop High
120 mm²269 A210 A5.79 V (1.4%)409.2 V9.55 V (2.3%)7523.4 WDrop High
150 mm²309 A241 A4.63 V (1.12%)410.4 V7.64 V (1.84%)6018.7 WDrop High
185 mm²353 A275 A3.76 V (0.91%)411.2 V6.2 V (1.49%)4880.1 WDrop High
240 mm²415 A324 A2.9 V (0.7%)412.1 V4.78 V (1.15%)3761.7 WDrop High
300 mm²477 A372 A2.32 V (0.56%)412.7 V3.82 V (0.92%)3009.4 WDrop High
400 mm²570 A445 A1.74 V (0.42%)413.3 V2.87 V (0.69%)2257.0 WDrop High

FAQ — 750 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 750A at 25 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 750A over 25m at 415V (voltage drop: 0.87V or 0.21%).

What is the power capacity of 750A at 415V?

At unity power factor, 750A at 415V supports 539.1 kW with a standard 800A circuit breaker.