80 Amp Cable Size at 30 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 30 m (98.4 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 3.56V (0.52%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 4.19V (0.61%)
Voltage at Load686.4 VLine Loss: 493.1 W
Max Power & Breaker95.61 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A59.31 V (8.59%)630.7 V97.83 V (14.18%)8217.6 WDrop High
2.5 mm²24 A18 A35.58 V (5.16%)654.4 V58.7 V (8.51%)4930.6 WDrop High
4 mm²32 A25 A22.24 V (3.22%)667.8 V36.68 V (5.32%)3081.6 WDrop High
6 mm²41 A32 A14.83 V (2.15%)675.2 V24.46 V (3.54%)2054.4 WDrop High
10 mm²57 A44 A8.9 V (1.29%)681.1 V14.67 V (2.13%)1232.6 WDrop High
16 mm²76 A59 A5.56 V (0.81%)684.4 V9.17 V (1.33%)770.4 WDrop High
25 mm²101 A78 A3.56 V (0.52%)686.4 V5.87 V (0.85%)493.1 W✓ OK (≤3%)
35 mm²125 A97 A2.54 V (0.37%)687.5 V4.19 V (0.61%)352.2 W✓ OK (≤3%)
50 mm²151 A118 A1.78 V (0.26%)688.2 V2.93 V (0.43%)246.5 W✓ OK (≤3%)
70 mm²192 A150 A1.27 V (0.18%)688.7 V2.1 V (0.3%)176.1 W✓ OK (≤3%)
95 mm²232 A181 A0.94 V (0.14%)689.1 V1.54 V (0.22%)129.8 W✓ OK (≤3%)
120 mm²269 A210 A0.74 V (0.11%)689.3 V1.22 V (0.18%)102.7 W✓ OK (≤3%)
150 mm²309 A241 A0.59 V (0.09%)689.4 V0.98 V (0.14%)82.2 W✓ OK (≤3%)
185 mm²353 A275 A0.48 V (0.07%)689.5 V0.79 V (0.11%)66.6 W✓ OK (≤3%)
240 mm²415 A324 A0.37 V (0.05%)689.6 V0.61 V (0.09%)51.4 W✓ OK (≤3%)
300 mm²477 A372 A0.3 V (0.04%)689.7 V0.49 V (0.07%)41.1 W✓ OK (≤3%)
400 mm²570 A445 A0.22 V (0.03%)689.8 V0.37 V (0.05%)30.8 W✓ OK (≤3%)

FAQ — 80 Amp Cable Size at 30 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 80A at 30 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 80A over 30m at 690V (voltage drop: 3.56V or 0.52%).

What is the power capacity of 80A at 690V?

At unity power factor, 80A at 690V supports 95.61 kW with a standard 80A circuit breaker.