80 Amp Cable Size at 60 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 60 m (196.9 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 7.12V (1.03%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 8.39V (1.22%)
Voltage at Load682.9 VLine Loss: 986.1 W
Max Power & Breaker95.61 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A118.61 V (17.19%)571.4 V195.65 V (28.36%)16435.2 WDrop High
2.5 mm²24 A18 A71.17 V (10.31%)618.8 V117.39 V (17.01%)9861.1 WDrop High
4 mm²32 A25 A44.48 V (6.45%)645.5 V73.37 V (10.63%)6163.2 WDrop High
6 mm²41 A32 A29.65 V (4.3%)660.3 V48.91 V (7.09%)4108.8 WDrop High
10 mm²57 A44 A17.79 V (2.58%)672.2 V29.35 V (4.25%)2465.3 WDrop High
16 mm²76 A59 A11.12 V (1.61%)678.9 V18.34 V (2.66%)1540.8 WDrop High
25 mm²101 A78 A7.12 V (1.03%)682.9 V11.74 V (1.7%)986.1 W✓ OK (≤3%)
35 mm²125 A97 A5.08 V (0.74%)684.9 V8.39 V (1.22%)704.4 W✓ OK (≤3%)
50 mm²151 A118 A3.56 V (0.52%)686.4 V5.87 V (0.85%)493.1 W✓ OK (≤3%)
70 mm²192 A150 A2.54 V (0.37%)687.5 V4.19 V (0.61%)352.2 W✓ OK (≤3%)
95 mm²232 A181 A1.87 V (0.27%)688.1 V3.09 V (0.45%)259.5 W✓ OK (≤3%)
120 mm²269 A210 A1.48 V (0.21%)688.5 V2.45 V (0.35%)205.4 W✓ OK (≤3%)
150 mm²309 A241 A1.19 V (0.17%)688.8 V1.96 V (0.28%)164.4 W✓ OK (≤3%)
185 mm²353 A275 A0.96 V (0.14%)689.0 V1.59 V (0.23%)133.3 W✓ OK (≤3%)
240 mm²415 A324 A0.74 V (0.11%)689.3 V1.22 V (0.18%)102.7 W✓ OK (≤3%)
300 mm²477 A372 A0.59 V (0.09%)689.4 V0.98 V (0.14%)82.2 W✓ OK (≤3%)
400 mm²570 A445 A0.44 V (0.06%)689.6 V0.73 V (0.11%)61.6 W✓ OK (≤3%)

FAQ — 80 Amp Cable Size at 60 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 80A at 60 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 80A over 60m at 690V (voltage drop: 7.12V or 1.03%).

What is the power capacity of 80A at 690V?

At unity power factor, 80A at 690V supports 95.61 kW with a standard 80A circuit breaker.