⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

80 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 0.59V (0.09%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 0.7V (0.1%)
Voltage at Load689.4 VLine Loss: 82.2 W
Max Power & Breaker95.61 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A9.88 V (1.43%)680.1 V16.3 V (2.36%)1369.6 WDrop High
2.5 mm²24 A18 A5.93 V (0.86%)684.1 V9.78 V (1.42%)821.8 WDrop High
4 mm²32 A25 A3.71 V (0.54%)686.3 V6.11 V (0.89%)513.6 WDrop High
6 mm²41 A32 A2.47 V (0.36%)687.5 V4.08 V (0.59%)342.4 WDrop High
10 mm²57 A44 A1.48 V (0.21%)688.5 V2.45 V (0.35%)205.4 WDrop High
16 mm²76 A59 A0.93 V (0.13%)689.1 V1.53 V (0.22%)128.4 WDrop High
25 mm²101 A78 A0.59 V (0.09%)689.4 V0.98 V (0.14%)82.2 W✓ OK (≤3%)
35 mm²125 A97 A0.42 V (0.06%)689.6 V0.7 V (0.1%)58.7 W✓ OK (≤3%)
50 mm²151 A118 A0.3 V (0.04%)689.7 V0.49 V (0.07%)41.1 W✓ OK (≤3%)
70 mm²192 A150 A0.21 V (0.03%)689.8 V0.35 V (0.05%)29.3 W✓ OK (≤3%)
95 mm²232 A181 A0.16 V (0.02%)689.8 V0.26 V (0.04%)21.6 W✓ OK (≤3%)
120 mm²269 A210 A0.12 V (0.02%)689.9 V0.2 V (0.03%)17.1 W✓ OK (≤3%)
150 mm²309 A241 A0.1 V (0.01%)689.9 V0.16 V (0.02%)13.7 W✓ OK (≤3%)
185 mm²353 A275 A0.08 V (0.01%)689.9 V0.13 V (0.02%)11.1 W✓ OK (≤3%)
240 mm²415 A324 A0.06 V (0.01%)689.9 V0.1 V (0.01%)8.6 W✓ OK (≤3%)
300 mm²477 A372 A0.05 V (0.01%)690.0 V0.08 V (0.01%)6.8 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.01%)690.0 V0.06 V (0.01%)5.1 W✓ OK (≤3%)

FAQ — 80 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 80A at 5 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 80A over 5m at 690V (voltage drop: 0.59V or 0.09%).

What is the power capacity of 80A at 690V?

At unity power factor, 80A at 690V supports 95.61 kW with a standard 80A circuit breaker.