80 Amp Cable Size at 70 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 70 m (229.7 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 1.3V (2.7%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 1.32V (2.75%)
Voltage at Load46.7 VLine Loss: 103.6 W
Max Power & Breaker3.84 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A159.79 V (332.89%)0.0 V263.57 V (549.11%)12782.9 WDrop High
2.5 mm²24 A18 A95.87 V (199.73%)0.0 V158.14 V (329.47%)7669.8 WDrop High
4 mm²32 A25 A59.92 V (124.83%)0.0 V98.84 V (205.92%)4793.6 WDrop High
6 mm²41 A32 A39.95 V (83.22%)8.1 V65.89 V (137.28%)3195.7 WDrop High
10 mm²57 A44 A23.97 V (49.93%)24.0 V39.54 V (82.37%)1917.4 WDrop High
16 mm²76 A59 A14.98 V (31.21%)33.0 V24.71 V (51.48%)1198.4 WDrop High
25 mm²101 A78 A9.59 V (19.97%)38.4 V15.81 V (32.95%)767.0 WDrop High
35 mm²125 A97 A6.85 V (14.27%)41.2 V11.3 V (23.53%)547.8 WDrop High
50 mm²151 A118 A4.79 V (9.99%)43.2 V7.91 V (16.47%)383.5 WDrop High
70 mm²192 A150 A3.42 V (7.13%)44.6 V5.65 V (11.77%)273.9 WDrop High
95 mm²232 A181 A2.52 V (5.26%)45.5 V4.16 V (8.67%)201.8 WDrop High
120 mm²269 A210 A2.0 V (4.16%)46.0 V3.29 V (6.86%)159.8 W~ ≤5%
150 mm²309 A241 A1.6 V (3.33%)46.4 V2.64 V (5.49%)127.8 W~ ≤5%
185 mm²353 A275 A1.3 V (2.7%)46.7 V2.14 V (4.45%)103.6 W✓ OK (≤3%)
240 mm²415 A324 A1.0 V (2.08%)47.0 V1.65 V (3.43%)79.9 W✓ OK (≤3%)
300 mm²477 A372 A0.8 V (1.66%)47.2 V1.32 V (2.75%)63.9 W✓ OK (≤3%)
400 mm²570 A445 A0.6 V (1.25%)47.4 V0.99 V (2.06%)47.9 W✓ OK (≤3%)

FAQ — 80 Amp Cable Size at 70 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 80A at 70 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 80A over 70m at 48V (voltage drop: 1.3V or 2.7%).

What is the power capacity of 80A at 48V?

At unity power factor, 80A at 48V supports 3.84 kW with a standard 80A circuit breaker.