⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

80 Amp Cable Size at 400 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)5× 400 mm²Drop: 0.68V (2.85%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.65V (23.53%)
Voltage at Load23.3 VLine Loss: 54.8 W
Max Power & Breaker1.92 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A913.07 V (3804.44%)0.0 V1506.13 V (6275.56%)73045.3 WDrop High
2.5 mm²24 A18 A547.84 V (2282.67%)0.0 V903.68 V (3765.33%)43827.2 WDrop High
4 mm²32 A25 A342.4 V (1426.67%)0.0 V564.8 V (2353.33%)27392.0 WDrop High
6 mm²41 A32 A228.27 V (951.11%)0.0 V376.53 V (1568.89%)18261.3 WDrop High
10 mm²57 A44 A136.96 V (570.67%)0.0 V225.92 V (941.33%)10956.8 WDrop High
16 mm²76 A59 A85.6 V (356.67%)0.0 V141.2 V (588.33%)6848.0 WDrop High
25 mm²101 A78 A54.78 V (228.27%)0.0 V90.37 V (376.53%)4382.7 WDrop High
35 mm²125 A97 A39.13 V (163.05%)0.0 V64.55 V (268.95%)3130.5 WDrop High
50 mm²151 A118 A27.39 V (114.13%)0.0 V45.18 V (188.27%)2191.4 WDrop High
70 mm²192 A150 A19.57 V (81.52%)4.4 V32.27 V (134.48%)1565.3 WDrop High
95 mm²232 A181 A14.42 V (60.07%)9.6 V23.78 V (99.09%)1153.3 WDrop High
120 mm²269 A210 A11.41 V (47.56%)12.6 V18.83 V (78.44%)913.1 WDrop High
150 mm²309 A241 A9.13 V (38.04%)14.9 V15.06 V (62.76%)730.5 WDrop High
185 mm²353 A275 A7.4 V (30.85%)16.6 V12.21 V (50.88%)592.3 WDrop High
240 mm²415 A324 A5.71 V (23.78%)18.3 V9.41 V (39.22%)456.5 WDrop High
300 mm²477 A372 A4.57 V (19.02%)19.4 V7.53 V (31.38%)365.2 WDrop High
400 mm²570 A445 A3.42 V (14.27%)20.6 V5.65 V (23.53%)273.9 WDrop High

FAQ — 80 Amp Cable Size at 400 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 80A at 400 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 5× 400 mm² copper cable for 80A over 400m at 24V (voltage drop: 0.68V or 2.85%).

What is the power capacity of 80A at 24V?

At unity power factor, 80A at 24V supports 1.92 kW with a standard 80A circuit breaker.