80 Amp Cable Size at 45 Meters (24V DC (Off-Grid Solar / Industrial Control))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 45 m (147.6 ft).
Copper Cable (≤3% Drop)240 mm²Drop: 0.64V (2.67%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.64V (2.65%)
Voltage at Load23.4 VLine Loss: 51.4 W
Max Power & Breaker1.92 kW80A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 45m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 102.72 V (428.0%) | 0.0 V | 169.44 V (706.0%) | 8217.6 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 61.63 V (256.8%) | 0.0 V | 101.66 V (423.6%) | 4930.6 W | Drop High |
| 4 mm² | 32 A | 25 A | 38.52 V (160.5%) | 0.0 V | 63.54 V (264.75%) | 3081.6 W | Drop High |
| 6 mm² | 41 A | 32 A | 25.68 V (107.0%) | 0.0 V | 42.36 V (176.5%) | 2054.4 W | Drop High |
| 10 mm² | 57 A | 44 A | 15.41 V (64.2%) | 8.6 V | 25.42 V (105.9%) | 1232.6 W | Drop High |
| 16 mm² | 76 A | 59 A | 9.63 V (40.12%) | 14.4 V | 15.88 V (66.19%) | 770.4 W | Drop High |
| 25 mm² | 101 A | 78 A | 6.16 V (25.68%) | 17.8 V | 10.17 V (42.36%) | 493.1 W | Drop High |
| 35 mm² | 125 A | 97 A | 4.4 V (18.34%) | 19.6 V | 7.26 V (30.26%) | 352.2 W | Drop High |
| 50 mm² | 151 A | 118 A | 3.08 V (12.84%) | 20.9 V | 5.08 V (21.18%) | 246.5 W | Drop High |
| 70 mm² | 192 A | 150 A | 2.2 V (9.17%) | 21.8 V | 3.63 V (15.13%) | 176.1 W | Drop High |
| 95 mm² | 232 A | 181 A | 1.62 V (6.76%) | 22.4 V | 2.68 V (11.15%) | 129.8 W | Drop High |
| 120 mm² | 269 A | 210 A | 1.28 V (5.35%) | 22.7 V | 2.12 V (8.82%) | 102.7 W | Drop High |
| 150 mm² | 309 A | 241 A | 1.03 V (4.28%) | 23.0 V | 1.69 V (7.06%) | 82.2 W | ~ ≤5% |
| 185 mm² | 353 A | 275 A | 0.83 V (3.47%) | 23.2 V | 1.37 V (5.72%) | 66.6 W | ~ ≤5% |
| 240 mm² | 415 A | 324 A | 0.64 V (2.67%) | 23.4 V | 1.06 V (4.41%) | 51.4 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.51 V (2.14%) | 23.5 V | 0.85 V (3.53%) | 41.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.39 V (1.6%) | 23.6 V | 0.64 V (2.65%) | 30.8 W | ✓ OK (≤3%) |
FAQ — 80 Amp Cable Size at 45 Meters (24V DC (Off-Grid Solar / Industrial Control))
What mm² cable size is required for 80A at 45 meters (24V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 80A over 45m at 24V (voltage drop: 0.64V or 2.67%).
What is the power capacity of 80A at 24V?
At unity power factor, 80A at 24V supports 1.92 kW with a standard 80A circuit breaker.
Related Lengths & Currents (24V)
80A · 5m (24V)80A · 10m (24V)80A · 15m (24V)80A · 20m (24V)80A · 25m (24V)80A · 30m (24V)80A · 35m (24V)80A · 40m (24V)80A · 50m (24V)80A · 60m (24V)80A · 70m (24V)10A · 45m (24V)16A · 45m (24V)20A · 45m (24V)25A · 45m (24V)32A · 45m (24V)40A · 45m (24V)50A · 45m (24V)63A · 45m (24V)100A · 45m (24V)125A · 45m (24V)160A · 45m (24V)200A · 45m (24V)