80 Amp Cable Size at 10 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 0.68V (2.85%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 0.59V (2.48%)
Voltage at Load23.3 VLine Loss: 54.8 W
Max Power & Breaker1.92 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A22.83 V (95.11%)1.2 V37.65 V (156.89%)1826.1 WDrop High
2.5 mm²24 A18 A13.7 V (57.07%)10.3 V22.59 V (94.13%)1095.7 WDrop High
4 mm²32 A25 A8.56 V (35.67%)15.4 V14.12 V (58.83%)684.8 WDrop High
6 mm²41 A32 A5.71 V (23.78%)18.3 V9.41 V (39.22%)456.5 WDrop High
10 mm²57 A44 A3.42 V (14.27%)20.6 V5.65 V (23.53%)273.9 WDrop High
16 mm²76 A59 A2.14 V (8.92%)21.9 V3.53 V (14.71%)171.2 WDrop High
25 mm²101 A78 A1.37 V (5.71%)22.6 V2.26 V (9.41%)109.6 WDrop High
35 mm²125 A97 A0.98 V (4.08%)23.0 V1.61 V (6.72%)78.3 W~ ≤5%
50 mm²151 A118 A0.68 V (2.85%)23.3 V1.13 V (4.71%)54.8 W✓ OK (≤3%)
70 mm²192 A150 A0.49 V (2.04%)23.5 V0.81 V (3.36%)39.1 W✓ OK (≤3%)
95 mm²232 A181 A0.36 V (1.5%)23.6 V0.59 V (2.48%)28.8 W✓ OK (≤3%)
120 mm²269 A210 A0.29 V (1.19%)23.7 V0.47 V (1.96%)22.8 W✓ OK (≤3%)
150 mm²309 A241 A0.23 V (0.95%)23.8 V0.38 V (1.57%)18.3 W✓ OK (≤3%)
185 mm²353 A275 A0.19 V (0.77%)23.8 V0.31 V (1.27%)14.8 W✓ OK (≤3%)
240 mm²415 A324 A0.14 V (0.59%)23.9 V0.24 V (0.98%)11.4 W✓ OK (≤3%)
300 mm²477 A372 A0.11 V (0.48%)23.9 V0.19 V (0.78%)9.1 W✓ OK (≤3%)
400 mm²570 A445 A0.09 V (0.36%)23.9 V0.14 V (0.59%)6.8 W✓ OK (≤3%)

FAQ — 80 Amp Cable Size at 10 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 80A at 10 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 80A over 10m at 24V (voltage drop: 0.68V or 2.85%).

What is the power capacity of 80A at 24V?

At unity power factor, 80A at 24V supports 1.92 kW with a standard 80A circuit breaker.