80 Amp Cable Size at 400 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 9.88V (2.38%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 10.58V (2.55%)
Voltage at Load405.1 VLine Loss: 1369.6 W
Max Power & Breaker57.5 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A790.74 V (190.54%)0.0 V1304.35 V (314.3%)109568.0 WDrop High
2.5 mm²24 A18 A474.44 V (114.32%)0.0 V782.61 V (188.58%)65740.8 WDrop High
4 mm²32 A25 A296.53 V (71.45%)118.5 V489.13 V (117.86%)41088.0 WDrop High
6 mm²41 A32 A197.68 V (47.63%)217.3 V326.09 V (78.58%)27392.0 WDrop High
10 mm²57 A44 A118.61 V (28.58%)296.4 V195.65 V (47.15%)16435.2 WDrop High
16 mm²76 A59 A74.13 V (17.86%)340.9 V122.28 V (29.47%)10272.0 WDrop High
25 mm²101 A78 A47.44 V (11.43%)367.6 V78.26 V (18.86%)6574.1 WDrop High
35 mm²125 A97 A33.89 V (8.17%)381.1 V55.9 V (13.47%)4695.8 WDrop High
50 mm²151 A118 A23.72 V (5.72%)391.3 V39.13 V (9.43%)3287.0 WDrop High
70 mm²192 A150 A16.94 V (4.08%)398.1 V27.95 V (6.74%)2347.9 W~ ≤5%
95 mm²232 A181 A12.49 V (3.01%)402.5 V20.59 V (4.96%)1730.0 W~ ≤5%
120 mm²269 A210 A9.88 V (2.38%)405.1 V16.3 V (3.93%)1369.6 W✓ OK (≤3%)
150 mm²309 A241 A7.91 V (1.91%)407.1 V13.04 V (3.14%)1095.7 W✓ OK (≤3%)
185 mm²353 A275 A6.41 V (1.54%)408.6 V10.58 V (2.55%)888.4 W✓ OK (≤3%)
240 mm²415 A324 A4.94 V (1.19%)410.1 V8.15 V (1.96%)684.8 W✓ OK (≤3%)
300 mm²477 A372 A3.95 V (0.95%)411.0 V6.52 V (1.57%)547.8 W✓ OK (≤3%)
400 mm²570 A445 A2.97 V (0.71%)412.0 V4.89 V (1.18%)410.9 W✓ OK (≤3%)

FAQ — 80 Amp Cable Size at 400 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 80A at 400 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 80A over 400m at 415V (voltage drop: 9.88V or 2.38%).

What is the power capacity of 80A at 415V?

At unity power factor, 80A at 415V supports 57.5 kW with a standard 80A circuit breaker.