10 Amp Cable Size at 400 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 9.27V (2.23%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 9.78V (2.36%)
Voltage at Load405.7 VLine Loss: 160.5 W
Max Power & Breaker7.19 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A98.84 V (23.82%)316.2 V163.04 V (39.29%)1712.0 WDrop High
2.5 mm²24 A18 A59.31 V (14.29%)355.7 V97.83 V (23.57%)1027.2 WDrop High
4 mm²32 A25 A37.07 V (8.93%)377.9 V61.14 V (14.73%)642.0 WDrop High
6 mm²41 A32 A24.71 V (5.95%)390.3 V40.76 V (9.82%)428.0 WDrop High
10 mm²57 A44 A14.83 V (3.57%)400.2 V24.46 V (5.89%)256.8 W~ ≤5%
16 mm²76 A59 A9.27 V (2.23%)405.7 V15.29 V (3.68%)160.5 W✓ OK (≤3%)
25 mm²101 A78 A5.93 V (1.43%)409.1 V9.78 V (2.36%)102.7 W✓ OK (≤3%)
35 mm²125 A97 A4.24 V (1.02%)410.8 V6.99 V (1.68%)73.4 W✓ OK (≤3%)
50 mm²151 A118 A2.97 V (0.71%)412.0 V4.89 V (1.18%)51.4 W✓ OK (≤3%)
70 mm²192 A150 A2.12 V (0.51%)412.9 V3.49 V (0.84%)36.7 W✓ OK (≤3%)
95 mm²232 A181 A1.56 V (0.38%)413.4 V2.57 V (0.62%)27.0 W✓ OK (≤3%)
120 mm²269 A210 A1.24 V (0.3%)413.8 V2.04 V (0.49%)21.4 W✓ OK (≤3%)
150 mm²309 A241 A0.99 V (0.24%)414.0 V1.63 V (0.39%)17.1 W✓ OK (≤3%)
185 mm²353 A275 A0.8 V (0.19%)414.2 V1.32 V (0.32%)13.9 W✓ OK (≤3%)
240 mm²415 A324 A0.62 V (0.15%)414.4 V1.02 V (0.25%)10.7 W✓ OK (≤3%)
300 mm²477 A372 A0.49 V (0.12%)414.5 V0.82 V (0.2%)8.6 W✓ OK (≤3%)
400 mm²570 A445 A0.37 V (0.09%)414.6 V0.61 V (0.15%)6.4 W✓ OK (≤3%)

FAQ — 10 Amp Cable Size at 400 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 10A at 400 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 10A over 400m at 415V (voltage drop: 9.27V or 2.23%).

What is the power capacity of 10A at 415V?

At unity power factor, 10A at 415V supports 7.19 kW with a standard 10A circuit breaker.